Chapter 2 Hardware Specifications and W iring 2-3 Terminal Description c Response c Maximum input haracteristi Current Voltag e X0.0+, X0.0-, X0.1+, X0.1-, X0.2+, X0.2-, X0.3+, and X0.3- 1. They are differential input terminals. 2. Functions of the terminals: High-speed count: The terminals are the Reset input terminals for counter 0~counter 5. X0.0+ and X0.0- are for counter 0. X0.1+ and X0.1- are for counter 1. X0.2+ and X0.2- are for counter 2 and counter 4. X0.3+ and X0.3- are for counter 3 and counter 5. High-speed comparison and capture: The terminals can function as trigger signals for high-speed capture. 200 kHz 15 mA 5~24 V X0.8+, X0.8-, X0.9+, and X0.9- 1.
They are differential input terminals. 2. Functions of the terminals: Motion control: The terminals are for a manual pulse generator. High-speed count: The terminals are for counter 0. X0.8+ and X0.8- are the A-phase input terminals for counter 0. X0.9+ and X0.9- are the B-phase input terminals for counter 0. High-speed comparison and capture: The terminals can function as trigger signals for high-speed capture. Interrupt input terminals 200 kHz 15 mA 5~24 V