AH500 Operation Manual Electrical specifications AH10DNET-5A AH500 series CPU modules which are supported DeviceNet interface DeviceNet Communication AH10PFBM-5A AH500 series CPU module supported PROFIBUS-DP interface PROFIBUS-DP communication 2-55 Communication ICMP, IP, TCP, UDP, DHCP, NTP, Modbus TCP, SNMP, and SMTP protocol Item Specifications Supply voltage 5 V DC Electric energy 1.5 W consumption Insulation voltage 2,500 V DC Weight 139 g Item Specifications Model name AH500 series PLCs Item Specifications Transmission method CAN Electrical isolation 500 V DC Connector Removable connector (5.08 mm) The Delta standard cables UC-DN01Z-01A and UC-DN01Z-02A are recommended.
The communication cable should be away from the power cable and the shielded cable should be connected to the ground. Communication cable DeviceNet network provides 11~25 V direct current. e.g. 28 mA (Typical value), 125 mA impulse current (24 V DC). Voltage Item Specifications Master mode: Supporting explicit messages, and all kinds of I/O connections with the slave such as I/O polled connections, bit-strobed connections, state changing connections, and cyclic connections Slave mode: Supporting explicit messages and a group 2 only server Message type Standard: 125 kbps, 250 kbps and 500 kbps Extension:
10 kbps, 20 kbps, 50 kbps, 125 kbps, 250 kbps, 500 kbps, 800 kbps and 1M bps Transmission speed Weight 135g Item Specifications Model name AH500 series PLCs Item Specifications Interface DB9 connector Transmission High-speed RS-485 method Transmission cable Two-wire twisted shielded cable Electrical isolation 500 V DC Item Specifications Message type Cyclic data exchange