Delta Electronics — 6.17.2 Explanation of Real-time Clock Instructions

AS Series Programming Manual Example 3 Enable DST function and in mode 2. Set the DST to start from the 2 nd Wednesday of May and to end on 3 rd Friday of September and the duration is 60 minutes. Setting values and descriptions: _6 Enable contact M0 Y0.0=ON, indicating DST function is enabled. For the year 2017, the 2 nd Wednesday of May is 10 th May and the 3 rd Friday of September is 15 th September. The PLC system time adds 60 minutes when the date May 10 th arrives and subtracts 60 minutes when the date September 15 th arrives to end daylight saving time. 6-516 Device Setting Value Description D0 3 The DST state is ON and in mode 2. D1 5 Starting month: May D2 2 Starting week number:

the 2nd week D3 3 Starting day: Wednesday D11 9 Ending month: September D12 3 Ending week number: the 3rd week D13 5 Ending day: Friday D20 60 Duration: 60 minutes