Chapter 6 Applied Instructions Example 2 When M0 is ON, the 8 output signals from Y0 – Y7 are sent to the output terminals. The output signals are refreshed immediately without waiting for the END instruction to be executed. Additional remarks 1. If D + n -1 exceeds the device range, the instruction is not executed, SM0 is ON, and the error code in SR0 is 16#2003. Example 3 1. During the execution of this instruction, if the external interrupt input is received through X0 6_ 6-173 Value in n D device Action Descriptions n = 1 High-speed output point Y0 Refresh new pulse positon Y0 immediately (SR460) n = 0 High-speed output point Y2 Without output completion auto-reset flag 1.
Stop high-speed Y2 outputting 2. Set the stop flag SM483 to ON 3. Refresh the current corresponding output position SR480 n = 0 High-speed output point Y4 With output completion auto-reset flag SM510 1. Set the output completion auto-reset flag SM510 to OFF 2. Refresh the current corresponding output position. SR500