omron — o4: Maintenance Monitor Settings

5.9 o: Operator Related Settings 0: READ Prohibited The data in the operator are write protected. The READ operation cannot be performed. 1: READ Permitted The data in the operator are not write protected. The READ operation can be performed. u o4: Maintenance Monitor Settings n o4-01: Accumulated Operation Time Setting Parameter o4-01 sets the cumulative operation time and allows the user to set the starting value of the accumulated operation time displayed in monitor U4-01. Note: The value in o4-01 is set in 10 h units. For example, a setting of 30 will set the cumulative operation time counter to 300 h. 300 h will also be displayed in monitor U4-01. n o4-02:

Accumulated Operation Time Selection Selects the conditions for what is to be considered “accumulated operation time.” Accumulated operation time is displayed in U4-01. Setting 0: Power On Time The drive logs the time it is connected to a power supply, no matter if the motor is running or not. Setting 1: Run Time The drive logs the time that the output is active, i.e., whenever a Run command is active (even if the motor is not rotating) or a voltage is output. n o4-03: Cooling Fan Maintenance Setting Sets the value of the cooling fan operation time base value used for the maintenance value displayed in U4-04. Be sure to reset this parameter back to 0 if the cooling fan is replaced. Note: 1.

The value in o4-03 is set in 10 h units. 2. The actual maintenance time depends on the environment the drive is used in. n o4-05: Capacitor Maintenance Setting Sets value of the maintenance monitor for the DC bus capacitors displayed in U4-05 as a percentage of the total expected performance life. This value should be reset to 0 when the DC bus capacitors have been replaced. Note: The actual maintenance time will depend on the environment the drive is used in. n o4-07: DC Bus Pre-charge Relay Maintenance Setting Sets the value of the softcharge bypass relay maintenance time displayed in U4-06 as a percentage of the total expected performance life.

This value should be reset to 0 when the relay has been replaced. Note: The maintenance actual time depends on the environment the drive is used in. n o4-09: IGBT Maintenance Setting Sets the value of the IGBT maintenance time displayed in U4-07 as a percentage of the total expected performance life. This value should be reset to 0 when the IGBTs have been replaced. Note: The actual maintenance time depends on the environment the drive is used in. 114 SIEP C710606 33A OYMC AC Drive – J1000 User Manual No. Name Setting Range Default o4-01 Accumulated Operation Time Setting 0 to 9999 0 No. Name Setting Range Default o4-02 Accumulated Operation Time Selection 0 or 1 0 No.

Name Setting Range Default o4-03 Cooling Fan Operation Time 0 to 9999 0 No. Name Setting Range Default o4-05 Capacitor Maintenance Setting 0 to 150% 0% No. Name Setting Range Default o4-07 DC Bus Pre-charge Relay Maintenance Setting 0 to 150% 0% No. Name Setting Range Default o4-09 IGBT Maintenance Setting 0 to 150% 0%