Siemens — Motor starter protector + contactor

© Siemens AG 2009 1) Guide value for 4-pole standard motors for 440 V AC, 50 Hz. Selection de- pends on the concrete startup and rated data of the protected motor. 2) Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible. Selection tables 440 V AC 40 Selection tables 440 V AC Motor starter protector + contactor CLASS 10, type of coordination 2, short-circuit breaking capacity I = 75 kA/100 kA q 440 V AC Standard induction motor 4-pole at 440 V AC1) Setting range Overload release Motor starter protec- tor Motor starter pro- tector Contactor2) Size Short-circuit break- ing capacity Iq Standard output P Motor current (guide value) I kW A A Order No. Order No.

kA 0.37 1.0 0.90 ... 1.25 3RV10 11-0KA10 3RT10 15-1AP01 S00/S00 100 0.55 1.4 1.10 ... 1.60 3RV10 11-1AA10 3RT10 15-1AP01 S00/S00 100 0.75 1.7 1.40 ... 2.00 3RV10 11-1BA10 3RT10 15-1AP01 S00/S00 100 1.1 2.5 2.20 ... 3.20 3RV10 21-1DA10 3RT10 26-1AP00 S0/S0 100 1.5 3.3 2.80 ... 4.00 3RV10 21-1EA10 3RT10 26-1AP00 S0/S0 100 2.2 4.6 3.50 ... 5.00 3RV10 21-1FA10 3RT10 26-1AP00 S0/S0 100 3 5.9 5.5 0... 8.00 3RV10 21-1HA10 3RT10 26-1AP00 S0/S0 100 4 7.7 7.00 ... 10.0 3RV10 21-1JA10 3RT10 26-1AP00 S0/S0 100 5.5 10.5 9.0 ... 12.5 3RV10 21-1KA10 3RT10 26-1AP00 S0/S0 100 7.5 14.0 11.0 ... 16.0 3RV10 21-4AA10 3RT10 26-1AP00 S0/S0 100 9 16.9 14.0 ...

20.0 3RV10 31-4BA10 3RT10 34-1AP00 S2/S2 100 11 20 18.0 ... 25.0 3RV10 31-4DA10 3RT10 34-1AP00 S2/S2 100 15 26 22.0 ... 32.0 3RV10 31-4EA10 3RT10 35-1AP00 S2/S2 100 18.5 32 28.0 ... 40.0 3RV10 31-4FA10 3RT10 35-1AP00 S2/S2 100 22 37 36.0 ... 45.0 3RV10 31-4GA10 3RT10 36-1AP00 S2/S2 100 30 50 45.0 ... 63.0 3RV10 41-4JA10 3RT10 44-1AP00 S3/S3 100 37 60 57.0 ... 75.0 3RV10 41-4KA10 3RT10 54-1AP36 S3/S6 100 45 73 70.0 ... 90.0 3RV10 41-4LA10 3RT10 54-1AP36 S3/S6 100 55 88 80.0 ... 100 3RV10 41-4MA10 3RT10 54-1AP36 S3/S6 100 75 120 64.0 ... 160 3RV10 63-7CL10 3RT10 55-6AP36 -/S6 100 90 145 64.0 ... 160 3RV10 63-7CL10 3RT10 56-6AP36 -/S6 100 110 177 80.0 ...

200 3RV10 63-7DL10 3RT10 64-6AP36 -/S10 100 132 209 160 ... 400 3RV10 73-7GL10 3RT10 65-6AP36 -/S10 100 160 255 160 ... 400 3RV10 73-7GL10 3RT10 66-6AP36 -/S10 100 185 318 252 ... 630 3RV10 83-7JL10 3RT12 75-6AP36 -/S12V 75 200 391 252 ... 630 3RV10 83-7JL10 3RT12 75-6AP36 -/S12V 75 250 491 252 ... 630 3RV10 83-7JL10 3RT12 76-6AP36 -/S12V 75