User Manual of EM730 Series Inverter Fig. 7-15 Schematic Diagram of Level and Single Pulse Output of Digital Output Terminal make a response with delay based on the function code settings. At present, the terminals Y1 and When the status of the selected function changes, the corresponding output terminal will R1 support this function. Details under default conditions: When the function changes from the invalid to valid status and is maintained with the valid delay, the corresponding output terminal will output the active level. When the function changes from the valid to invalid status and is maintained with the invalid delay, the corresponding output terminal will output the inactive level.
★ If the function code is set to 0.000s, the delay will be invalid. When one function output terminal is in the single pulse output mode (see F03.05 for details), the pulse width of the active level can be controlled by setting the single pulse output time, in order to meet different process or control requirements. 194 Function code Function code name Parameter description Unit Default setting Attribute Mailing address F03.17 Single pulse time of Y1 output 0.001 ~ 30.000 s 0.250 ● 0x0311 F03.19 Single pulse time of R1 output 0.001 ~ 30.000 s 0.250 ● 0x0312