User Manual of EM760 High-Performance Inverter By default, several common items are included in the cycle display queue, including the output frequency (F18.00), set frequency (F18.01), output current (F18.06), output voltage (F18.08) and DC bus voltage (F18.09). Please set the corresponding bit to 1 to select other display parameters and 0 to hide the selected parameters. F00.29 is used to set a password to enable the password protection and prevent the function code parameters of the inverter from modification by unauthorized personnel. If the password is set to 0, the password function will be invalid.
When anon-zero user password is set, all parameters (except this function code) can only be viewed and are not modifiable. 6.6.16 Upload and download Where several inverters need to run with the same parameter settings, we can debug one inverter first, set it to F12.03=1 to upload the set parameters to the keyboard for temporary storage and finally set the other inverters to F12.03=2 (no download for motor parameters) or F12.03 = 3 (download motor parameters) to download the parameters to these inverters. This function can be applied to quickly set the parameters of several inverters.
Even if some parameter settings are different, this function can be applied to set multiple function codes before setting by other means. 6.7 Monitoring This group of parameters is used only to view the current status of the inverter and cannot be changed. 159 Function code Function code name Parameter description Unit Default setting Attribute F00.29 User password 0~65535 0 O Function code Function codename Parameter description Unit Default setting Attribute F12.03 Parameter copying 0: No operation 1: parameter upload to keyboard 2: Download parameters to inverter (No download for F01 and F14) 3:
Download parameters to inverter 0 O Function code Function codename Parameter description Unit F18.00 Output frequency Display the current output frequency of the inverter. Scope: 0.00 to upper frequency limit. *: This parameter will be updated promptly in the speed control mode. Hz F18.01 Set frequency Display the current set frequency of the inverter. Scope: 0.00 to maximum frequency F00.16. *: This parameter will be updated promptly in the speed control mode. Hz F18.02 PG feedback frequency In case of FVC control or other control methods that involve a feedback encoder, PG card feedback frequency is displayed. Scope: 0.00 to upper frequency limit. *:
This parameter will be updated in real time only when the PG card is configured. Hz