User Manual of EM760 High-Performance Inverter 171 Function code Function codename Parameter description Unit Current value of application macro Attribute F00.02 Options of command source 0: keyboard control (LOC/REM indicator ON) 0 O F00.05 Options of auxiliary frequency source B 10: process PID 10 O F00.06 Options of frequency source 1: auxiliary frequency source B 1 O F00.14 Acceleration time 1 0.00~650.00(F15.13=0) s 10.00 ● F00.15 Deceleration time 1 0.00~650.00(F15.13=0) s 15.00 ● F00.19 Lower frequency limit 0.00 to upper frequency limit F00.18 Hz 0.00 ● F00.21 Reverse control 0: Allow forward/reverse running 1: Prohibit reversing 1 O F00.30 Model selection 0: G type 1:
P type 1 O F02.00 Options of X1 digital input function See the input terminal function table. 1 O F02.01 Options of X2 digital input function See the input terminal function table. 23 O F02.63 Selection of analog input AI2 type 0: 0~10V 0 O F03.00 Options of Y1 output function See function list of digital output terminals 59 ○ F03.02 Options of R1 output function See function list of digital output terminals 7 ○ F05.00 V/F curve setting 4: square V/F 4 O F07.06 Bus voltage control options Ones place: Instantaneous stop/no-stop function options 0: Invalid 1: deceleration 2: deceleration to stop Tens place: Overvoltage stall function options 0: Invalid 1:
valid 11 O F07.14 Number of retries after failure 0-20; 0: disable retry after failure 5 O F07.16 Interval of retries after failure 0.01~30.00 s 30 ● F09.01 Digital PID setting 0.0 to PID setting feedback range F09.03 bar 3.00 ● F09.02 PID feedback source 2: AI2 2 O