sinee — Chapter 11 Function Code Table

User Manual of EM760 High-Performance Inverter 298 ASR T2 _ 0.000: no integral F06.04 Switching frequency 1 0.00 to switching frequency 2 Hz 5.00 ● 0x0604 F06.05 Switching frequency 2 Switching frequency 1 to maximum frequency F00.16 Hz 10.00 ● 0x0605 F06.07 Filtering time constant of speed loop output 0.000~0.100 s 0.001 ● 0x0607 F06.08 Vector control slip gain 10.00~200.00 % 100.00 ● 0x0608 F06.09 Upper limit source selection of speed control torque 0: set by F06.10 and F06.11 1: AI1 2: AI2 3: AI3 4: AI4 (expansion card) 5: Communication setting (percentage) 6: Take the maximum values of AI2 and AI3 7:

Take the minimum values of AI2 and AI3 0 O 0x0609 F06.10 Upper limit of speed control motor torque 0.0~250.0 % 165.0 ● 0x060A F06.11 Upper limit of speed control brake torque 0.0~250.0 % 165.0 ● 0x060B F06.12 Excitation current proportional gain ACR-P1 0.00~100.00 0.50 ● 0x060C F06.13 Excitation current integral time constant ACR-T1 0.00~600.00 0.00: no integral ms 10.00 ● 0x060D F06.14 Torque current proportional gain ACR-P2 0.00~100.00 0.50 ● 0x060E F06.15 Torque current integral time constant ACR-T2 0.00~600.00 0.00: no integral ms 10.00 ● 0x060F F06.17 SVC zero- frequency processing 0: braking 2 O 0x0611