User Manual of EM760 High-Performance Inverter 312 F09.28 Sleep action point 0.00-100.00 (100.00 corresponds to the PID setting feedback range) % 100.00 ● 0x091C F09.29 Sleep delay time 0.0~6500.0 s 0.0 ● 0x091D F09.30 Wake-up action point 0.00-100.00 (100.00 corresponds to the PID setting feedback range) % 0.00 ● 0x091E F09.31 Wake-up delay time 0.0~6500.0 S 0.0 ● 0x091F F09.32 Multi-segment PID setting 1 0.0 to PID setting feedback range F09.03 0.0 ● 0x0920 F09.33 Multi-segment PID setting 2 0.0 to PID setting feedback range F09.03 0.0 ● 0x0921 F09.34 Multi-segment PID setting 3 0.0 to PID setting feedback range F09.03 0.0 ● 0x0922 F09.35 Lower limit of feedback voltage Lower limit of feedback voltage to 10.00 V 10.00 ● 0x0923 F09.36 Upper limit of feedback voltage 0.00 to upper limit of feedback voltage V 0.00 ● 0x0924 F09.37 Options of integral action within the set change time of PID 0:
Always calculate the integral term 1: Calculate the integral term after the F09.21 set time is reached 2: Calculate the integral term when the error is less than F09.38 0 ● 0x0925 F09.38 Input deviation of integral action within the set change time of PID 0.00~100.00 % 30 ● 0x0926 F09.39 Wake-up option 0: target pressure F09.01* coefficient of wake- up action point 1: Wake-up action point (F09.30) 0 O 0x0927 F09.40 Coefficient of wake-up action point 0.0-100.0 (100% corresponds to PID setting) % 90.0 ● 0x0928 F09.41 Pipeline network alarm overpressure 0.0 to pressure sensor range F09.03 bar 6.0 ● 0x0929 F09.42 Overpressure protection time 0-3600 (0:
invalid) s 0 ● 0x092A F09.43 PID reverse limit 0: Invalid 1: valid 0 O 0x092B F09.44 Sleep mode options 0: Sleep at sleep frequency (F09.45) 1: Sleep at sleep action points (F09.28) 0 O 0x092C