4-2 Function Mode 4 Functions *1. The Inverter's rated current is "1000". *2. The second decimal place is ignored when the value is over 10000 (100.0 seconds). 4-83 Register No. Function name Parameter No. R/W function Data Resolution 0084h FI start frequency A101 R/W 0 to Max. frequency 0.1 [Hz] 0085h FI end frequency A102 R/W 0 to Max. frequency 0.1 [Hz] 0086h FI start ratio A103 R/W 0 to 100 1. [%] 0087h FI end ratio A104 R/W 0 to 100 1. [%] 0088h FI start selection A105 R/W 0: External start frequency 1: 0 Hz  0089h Retry selection b001 R/W 0: Alarm 1: 0-Hz start 2: Frequency matching start 3:

Trip after frequency matching deceleration stop  008Ah Allowable momentary power interruption time b002 R/W 3 to 250 0.1 [s] 008Bh Retry wait time b003 R/W 3 to 1000 0.1 [s] 008Ch Momentary power interruption/undervoltage trip during stop selection b004 R/W 0: Disabled 1: Enabled  008Dh Momentary power interruption retry time selection b005 R/W 0: 16 times 1: No limit  008Eh Electronic thermal level b012 R/W 2000 to 12000 0.01 [%] 008Fh 2nd electronic thermal level b212 R/W 2000 to 12000 0.01 [%] 0090h Electronic thermal characteristics selection b013 R/W 0: Reduced torque characteristics 1 1: Constant torque characteristics 2:

Reduced torque characteristics 2 *1  0091h 2nd electronic thermal characteristics selection b213 R/W 0: Reduced torque characteristics 1 1: Constant torque characteristics 2: Reduced torque characteristics 2 *1  0092h Overload limit selection b021 R/W 0: Disabled 1: Enabled during acceleration/constant speed 2: Enabled during constant speed  0093h Overload limit level b022 R/W 5000 to 15000 *1 0.01 [%] 0094h Overload limit parameter b023 R/W 1 to 300 0.1 [s] 0095h Soft lock selection b031 R/W 0: Data other than b031 cannot be changed when terminal SFT is ON. 1: Data other than b031 and the specified frequency parameter cannot be changed when terminal SFT is ON. 2:

Data other than b031 cannot be changed. 3: Data other than b031 and specified frequency parameter cannot be changed.  0096h AM adjustment b080 R/W 0 to 255 1