omron — PID Feedback Value Monitor [d004]

4-1 Monitor Mode 4Functions 4-1 Monitor Mode Output Frequency Monitor [d001] Displays the output frequency of the Inverter. The monitor LED indicator "Hz" lights up while d001 is displayed. (Display) 0.0 to 400.0: Displays in increments of 0.1 Hz. 4 Output Current Monitor [d002] Functions Displays the output current value of the Inverter. The monitor LED indicator "A" lights up while d002 is displayed. (Display) 0.0 to 999.9: Displays in increments of 0.1 A. Rotation Direction Monitor [d003] Displays whether the Inverter output is in a forward/reverse/stop status. The RUN LED indicator lights up during forward/reverse rotation. (Display) F: Forward o: Stop r:

Reverse PID Feedback Value Monitor [d004] Displays a feedback value converted by [A075] (PID scale) when the PID function is enabled ([A071] = 01). "Monitor display" = "PID feedback value (%)" Ч "PID scale" [A075] (Setting) A071: 01 (PID enabled) A075: 0.01 to 99.99 (Can be set in increments of 0.01.) (Display) 0.00 to 99.99 : Displays in increments of 0.01. 100.0 to 999.9 : Displays in increments of 0.1. 1000 to 9999 : Displays in increments of 1. 4-1