omron — Modbus-RTU Method

4-4 Communication Function 4 Functions Note 1: The Inverter's rated current is "1000". Note 2: If the set value is "10000" (100.0 sec) or more, the value in the second decimal place is ignored. 4-170 Register No. Function name Function code R/W Monitor and setting parameters Resolution 0012h Fault monitor 1 factor d081 R See "Inverter Trip Factor List" (page 4-172).  0013h Fault monitor 1 Inverter status See "Inverter Trip Factor List" (page 4-172).

 0014h Fault monitor 1 frequency (HIGH) 0 to 40000 0.01 [Hz] 0015h Fault monitor 1 frequency (LOW) 0016h Fault monitor 1 current Output current value at the time of tripping 0.1 [A] 0017h Fault monitor 1 voltage DC input voltage at the time of tripping 1 [V] 0018h Fault monitor 1 RUN time (HIGH) Total RUN time before the trip 1 [h] 0019h Fault monitor 1 RUN time (LOW) 001Ah Fault monitor 1 ON time (HIGH) Total power ON time before the trip 1 [h] 001Bh Fault monitor 1 ON time (LOW) 001Ch Fault monitor 1 factor d082 R See "Inverter Trip Factor List" (page 4-172).  001Dh Fault monitor 1 Inverter status See "Inverter Trip Factor List" (page 4-172).

 001Eh Fault monitor 2 frequency (HIGH) 0 to 40000 0.01 [Hz] 001Fh Fault monitor 2 frequency (LOW) 0020h Fault monitor 2 current Output current value at the time of tripping 0.1 [A] 0021h Fault monitor 2 voltage DC input voltage at the time of tripping 1 [V] 0022h Fault monitor 2 RUN time (HIGH) Total RUN time before the trip 1 [h] 0023h Fault monitor 2 RUN time (LOW) 0024h Fault monitor 2 ON time (HIGH) Total power ON time before the trip 1 [h] 0025h Fault monitor 2 ON time (LOW) 0026h Fault monitor 3 factor d083 R See "Inverter Trip Factor List" (page 4-172).  0027h Fault monitor 3 Inverter status See "Inverter Trip Factor List" (page 4-172).

 0028h Fault monitor 3 frequency (HIGH) 0 to 40000 0.01 [Hz] 0029h Fault monitor 3 frequency (LOW) 002Ah Fault monitor 3 current Output current value at the time of tripping 0.1 [A] 002Bh Fault monitor 3 voltage DC input voltage at the time of tripping 1 [V] 002Ch Fault monitor 3 RUN time (HIGH) Total RUN time before the trip 1 [h] 002Dh Fault monitor 3 RUN time (LOW) 002Eh Fault monitor 3 ON time (HIGH) Total power ON time before the trip 1 [h] 002Fh Fault monitor 3 ON time (LOW)