4-4 Communication Function 4 Functions 4-184 Register No. Function name Function code R/W Monitor and setting parameters Resolution 1312h Free setting, electronic thermal frequency 2 b017 R/W 0 to 400 1 [Hz] 1313h Free setting, electronic thermal current 2 b018 R/W 0 to Rated current 0.1 [A] 1314h Free setting, electronic thermal frequency 3 b019 R/W 0 to 400 1 [Hz] 1315h Free setting, electronic thermal current 3 b020 R/W 0 to Rated current 0.1 [A] 1316h Overload limit selection b021 R/W 0: Disabled 1: Enabled during acceleration/constant speed 2: Enabled during constant speed 3:

Enabled during acceleration/constant speed (accelerated during regeneration)  1317h Overload limit level b022 R/W 200 to 2000 0.1 [%] 1318h Overload limit parameter b023 R/W 10 to 3000 0.01 [s] 1319h Overload limit selection 2 b024 R/W 0: Disabled 1: Enabled during acceleration/ constant speed 2: Enabled during constant speed 3: Enabled during acceleration/constant speed (accelerated during regenera- tion)  131Ah Overload limit level 2 b025 R/W 200 to 2000 0.1 [%] 131Bh Overload limit parameter 2 b026 R/W 10 to 3000 0.01 [s] 131Ch Overcurrent suppression function b027 R/W 0: Disabled 1:

Enabled  131Dh Frequency pull-in restart level b028 R/W 200 to 2000 0.1 [%] 131Eh Frequency pull-in restart parameter b029 R/W 10 to 3000 0.01 [s] 131Fh Starting frequency at frequency pull-in restart b030 R/W 0: Frequency at interruption 1: Max. frequency 2: Set frequency  1320h Soft lock selection b031 R/W 0: Data other than b031 cannot be changed when terminal SFT is ON. 1: Data other than b031 and the specified frequency parameter cannot be changed when terminal SFT is ON. 2: Data other than b031 cannot be changed. 3: Data other than b031 and the specified frequency parameter cannot be changed. 10: Data can be changed during RUN.  1321h Not used    1322h Not used   