4-4 Communication Function 4 Functions 4-188 Register No. Function name Function code R/W Monitor and setting parameters Resolution 135Ah STOP key selection b087 R/W 0: Enabled 1: Disabled 2: Disabled only during stop 135Bh Free-run stop selection b088 R/W 0: 0-Hz start 1: Frequency matching start 2: Frequency pull-in restart 135Ch Automatic carrier frequency reduction b089 R/W 0: Disabled 1: Enabled 135Dh Usage rate of regenerative braking function b090 R/W 0 to 1000 0.1 [%] 135Eh Stop selection b091 R/W 0: Deceleration → Stop 1: Free-run stop 135Fh Cooling fan control b092 R/W 0: Always ON 1:
ON during RUN 1360h Not used 1361h Not used 1362h Regenerative braking function operation selection b095 R/W 0: Disabled 1: Enabled (disabled during stop) 2: Enabled (also during stop) 1363h Regenerative braking function ON level b096 R/W 330 to 380 660 to 760 1 [V] 1364h Not used 1365h Thermistor selection b098 R/W 0: Disabled 1: PTC enabled 2:
NTC enabled 1366h Thermistor error level b099 R/W 0 to 9999 1 [Ω] 1367h Free V/f frequency 1 b100 R/W 0 to Free V/f frequency 2 1 [Hz] 1368h Free V/f voltage 1 b101 R/W 0 to 8000 0.1 [V] 1369h Free V/f frequency 2 b102 R/W 0 to Free V/f frequency 2 1 [Hz] 136Ah Free V/f voltage 2 b103 R/W 0 to 8000 0.1 [V] 136Bh Free V/f frequency 3 b104 R/W 0 to Free V/f frequency 2 1 [Hz] 136Ch Free V/f voltage 3 b105 R/W 0 to 8000 0.1 [V] 136Dh Free V/f frequency 4 b106 R/W 0 to Free V/f frequency 2 1 [Hz] 136Eh Free V/f voltage 4 b107 R/W 0 to 8000 0.1 [V] 136Fh Free V/f frequency 5 b108 R/W 0 to Free V/f frequency 2 1 [Hz] 1370h Free V/f voltage 5 b109 R/W 0 to 8000 0.1 [V] 1371h Free V/f frequency 6 b110 R/W 0 to Free V/f frequency 2 1 [Hz] 1372h Free V/f voltage 6 b111 R/W 0 to 8000 0.1 [V] 1373h Free V/f frequency 7 b112 R/W 0 to Free V/f frequency 2 1 [Hz] 1374h Free V/f voltage 7 b113 R/W 0 to 8000 0.1 [V]