AS Series Programming Manual 3. Follow the steps below for the basic settings on the panel of the ASD-A2. a. Set the servo parameter P2-08 to 10 to restore the factory settings. b. Power the servo off and back on again. c. Set P1-01 to 0001 (PR mode). d. Set P3-01 to 0400 and the baud rate of the servo for CANopen communication to 1.0 Mbps. The baud rate must be the same as that of the PLC. e. Set a station address for every servo, based on the number of servos. Set P3-00 of each servo to 1, 2, and 3 in order. You can set a maximum of eight servos. f. Power the servo off and back on again. _6 g. Begin operation after the basic setting is complete. 4.
Download the sample program and set M0 to ON. The instruction initializes the servos at station addresses 1–3. When SM1681 is ON, the initialization is complete. When the servo enters CANopen mode successfully, CO-LD information is displayed. Ladder diagram: Structured Texts programming language: 6-896