address Latched Register content b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 #30 H’4050 ╳ R Error status Register for storing all error status. See the table of error status for more information. b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 Default = H’0000. Take the setting of CH1 for example: 1. When b0 = 0, the user is allowed to tune CR#18 (OFFSET) and CR#24 (GAIN) of CH1. When b0 = 1, the user is not allowed to tune CR#18 (OFFSET) and CR#24 (GAIN) of CH1. 2. b1 represents whether the OFFSET/GAIN tuning registers are latched. b1 = 0 (default, latched); b1 = 1 (non-latched) 3. When b2 = 1, all settings will return to default values. (except CR#31, CR#32) CR#1:

The working mode of the four channels in the analog input module. There are 4 modes for each channel which can be set up separately. For example, if the user needs to set up CH1: mode 0 (b2 ~ b0 = 000); CH2: mode 1 (b5 ~ b3 = 001), CH3: mode 2 (b8 ~ b6 = 010) and CH4: mode 3 (b11 ~ b9 = 011), CR#1 has to be set as H’000A and the higher bits (b12 ~ b15) have to be reserved. Default value = H’0000. CR#18 ~ CR#21: The adjusted OFFSET value of CH1 ~ CH4 (default = K0, unit = LSB), representing the analog output voltage or current when the output digital value = 0 after calculation. The adjustable range: -2,000 ~ +2,000. 6. CR#24 ~ CR#2:

The adjusted GAIN value of CH1 ~ CH4 (default = K2,000, unit = LSB), representing the analog output voltage or current when the output digital value = 2,000 after calculation. reserved CH4 CH3 CH2 CH1 Default = H’0002. For setting up communication speed: 4,800 / 9,600 / 19,200 / reserved CH4 CH3 CH2 CH1 H’4054 ○ R Firmware version Displaying the current firmware version In hex; e.g. version 1.0A is indicated as CR#0: Model name. The user can read the model name from the program and see if the extension module exists. b14: High/low bit exchange of CRC checksum (only valid in RTU mode) #31 H’4051 ○ R/W Communication address setting For setting up RS-485 communication address. Range:

01 ~ 255 Default = K1 b15: Switch between ASCII/RTU mode. 0 = ASCII mode (default) CR#6 ~ CR#9: The output values of CH1 ~ CH4 (range: K0 ~ K4,000; default = K0; unit: LSB) #0 H’4032 ○ R Model name Set up by the system. DVP04DA-H2 model code = H’6401 Range of OFFSET at CH1 ~ CH4: K-2,000 ~ K2,000 ASCII data format: 7-bit, Even bit, 1 stop bit (7, E, 1) RTU data format: 8-bit, Even bit, 1 stop bit (8, E, 1) CR#2 ~ CR#5, CR#10 ~ CR#17, CR#22, CR#23, CR#28 and CR#29 are reserved. DVP04DA-H2 analog output module Description Range of output value at CH1 ~ CH4: K0 ~ K4,000 Range of GAIN at CH1 ~ CH4: K-1,600 ~ K8,000 Mode 2: Current output (4mA ~ 20mA) Mode 3: Current output (0mA ~ 20mA) b0:

4,800bps b1: 9,600bps (default) The adjustable range of voltage: -5V ~ +5V (-2,000 LSB ~ +2,000 LSB ) The adjustable range of current: -10mA ~ +10mA (-2,000 LSB ~ +2,000 LSB ) Output mode: Default = H’0000 Mode 0: Voltage output (0V ~ 10V) Mode 1: Voltage output (2V ~ 10V) 38,400 / 57,600 / 115,200bps b2: 19,200bps b3: 38,400bps b4: 57,600bps b5: 115,200bps Default = K0 (unit: LSB) Default = K0 (unit: LSB) Default = K2,000 (unit: LSB) LSB (Least Significant Bit): For voltage output 1 LSB = 10V/4,000 = 2.5mV 。 For current output 1 LSB = 20mA/4,000 = 5μA 。 b6 ~ b13: reserved For system use. R: Able to read data by FROM instruction or RS-485 communication W:

Able to write data by TO instruction or RS-485 communication #2 ~ #5 Reserved #10 ~ #17 Reserved #22 ~ #23 Reserved #28 ~ #29 Reserved H’010A. :

latched (when written in through RS-485 communication) Z Control Registers #1 H’4033 ○ R/W Output mode #6 H’4038 ╳ R/W CH1 output value #7 H’4039 ╳ R/W CH2 output value #8 H’403A ╳ R/W CH3 output value #9 H’403B ╳ R/W CH4 output value #18 H’4044 ○ R/W Adjusted OFFSET value of CH1 #19 H’4045 ○ R/W Adjusted OFFSET value of CH2 #20 H’4046 ○ R/W Adjusted OFFSET value of CH3 #21 H’4047 ○ R/W Adjusted OFFSET value of CH4 #24 H’404A ○ R/W Adjusted GAIN value of CH1 #25 H’404B ○ R/W Adjusted GAIN value of CH2 #26 H’404C ○ R/W Adjusted GAIN value of CH3 #27 H’404D ○ R/W Adjusted GAIN value of CH4 #32 H’4052 ○ R/W Communication speed (baud rate) Return to default setting; OFFSET/GAIN tuning authorization setting setting H’4053 ○ R/W CR# RS-485 parameter :

non-latched Explanations: 1. When performing analog output, please isolate other power wirings. 2. If the ripples at the loaded input terminal are too significant that causes noise interference on the wiring, connect the wiring to 0.1 ~ 0.47μF 25V capacitor. 3. Please connect the terminal on both the power modules and DVP04DA-H2 to the system earth point and ground the system contact or connect it to the cover of power distribution cabinet. 4.

DO NOT wire empty terminals Digital/Analog (4D/A) Module Voltage Output Current Output DC/DC +15V -15V AG (100 or less) CH1 CH1 0V~+10V *2 CH4 CH4 12 bits (1 ± converter 0 ~ 10V - Power supply voltage 24 VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%) V+ I+ COM FG V+ I+ COM FG 24+ 24- ± shielding cable *1 shielding cable *1 system grounding current output DC24V Analog output channel 4 channels/module voltage output 0mA~20mA *3 class 3 grounding AC drive, recorder, scale valve... AC drive, recorder, scale valve... terminal of power module Y Specifications 1.3 External Wiring 2.1. Functions Note:

http://www.delta.com.tw/industrialautomation/ 5011651101-D2E1 9 DVP04DA-H2 is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust, humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the device (e.g. key or specific tools are required to open the enclosure) in case danger and damage on the device may occur. 9 DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may occur. Check all the wiring again before switching on the power. 9 DO NOT tough any terminal when the power is switched on.

DO NOT touch any internal circuit in 1 minute after the power is switched off. 1.1 Model Explanation & Peripherals ™ Thank you for choosing Delta DVP series. DVP04DA-H2 is able to read and write data of DVP04DA-H2 analog signal output modules through FROM/TO instructions given by the program of DVP-EH2 series MPU. The analog signal output module receives 4 groups of 12-bit digital data from PLC MPU and converts the data into 4 points of analog signals for output in either voltage or current. 2007-01-15 ™ The user can select voltage or current output by wiring. Range of voltage output: 0V ~ +10VDC (resolution: 2.5mV). Range of current output: 0mA ~ 20mA (resolution: 5μA).

D - V + I + V + 24V 0V I + V + I + V + I + D + COM FG FG FG COM COM COM 1 DIN rail (35mm) 6 Terminals Analog Output Module 9 Make sure the groud terminal is correctly grounded in order to prevent electromagnetic interference. X Introduction CH1 CH2 CH3 CH4 RS-485 8 4 POWER, ERROR, D/A indicator 9 Mounting port for extension modules MADE IN XXXXXX ™ Model/Serial No.

Стр. 1

Read CR#24 of special module No.0 into D0 and CR#25 into D1. Only 2 groups of data is read at Use 32-bit instruction DTO to write the content in D11 and D10 into CR#7 and CR#6 of special module No.0. Only 1 group of data is written in at a time (n = 1). 1. : The No. of special modules connected to PLC MPU. No. 0 is the module closest to te MPU. Maximum 8 modules are allowed to connected to a PLC MPU and they will not occupy any I/O points. 2. : CR#. CR (control register) is the 49 16-bit memories built in the special module, numbered in decimal as #0 ~ #48. All operation status and settings of the special module are contained in the CR. 1.

When M1083 = Off, during the execution of FROM/TO instruction, all external or internal interruption subroutines will be forbidden. The interruptions are allowed only after FROM/TO instruction finishes its execution. FROM/TO instruction can also be used in an interruption subroutine. 2. When M1083 = On and an interruption signal occurs during the execution of FROM/TO instruction, the interruption will be processed first (with a 100us delay) and the execution of FROM/TO will be stopped. After the interruption subroutine finishes its execution, the program will jump to the next instructio of FROM/TO. FROM/TO cannot be used in an interruption subroutine.

The content of this instruction sheet may be revised without prior notice. Please consult our distributors or download the most updated version at http://www.delta.com.tw/industrialautomation : Data to be written into CR : Number of data to be written at a time 3. FROM/TO instruction is for reading/writing 1 CR at a time. DFROM/DTO instruction is for reading/writing 2 CRs at a time. 4. Number of groups “n” to be transmitted: n = 2 in 16-bit instructions and n = 1 in 32-bit instructions mean the same. Instruction Explanation : No. of special module (m1 = 0 ~ 7) : CR# in special module to be read : Device for storing read data :

Number of data to be read at a time 79 D T O P Write CR data into special modules Instruction Explanation : No. of special module (m1 = 0 ~ 7) : CR# in special module to be written Designated device Designated device Designated CR 32-bit instruction when n=3 78 D F R O M P Read CR data in special modules Designated CR number FROM K0 K24 D0 K2 DTO K0 K6 D10 K1 D0 D1 D2 D3 D4 D5 M1083 for switching instruction modes in EH2 series models ] Relevant Instructions Higher 16-bit a time (n = 2).

Operand rules D0 D1 D2 D3 D4 D5 X0 X0 Program Example Program Example Remarks API API ѓ Write H’10 into CR#1 of analog output module No.1 and set CH1 in mode 0 (voltage output 0V ~ +10V) and CH2 in mode 2 (current output 4mA ~ +20mA). ѓ Write H’0 into CR#33 and allow OFFSET/GAIN tuning in CH1 ~ CH4 ѓ When X0 goes from Off to On, write the OFFSET value K0 LSB into CR#18 and the GAIN value K1,000 LSB into CR#24.

ѓ Write H’18 into CR#1 of analog output module No.1 and set CH1 in mode 0 (voltage output 0V Write H’0 into CR#33 and allow OFFSET/GAIN tuning in CH1 ~ CH4 ~ +10V) and CH2 in mode 3 (current output When X0 goes from Off to On, write the OFFSET value K400 LSB into CR#19 and the GAIN value K3,600 LSB into CR#25. When the module is powered for the first time, POWER LED will be on. After ERROR LED being on for 0.5 4. When the input or output value exceeds the upper bound or falls below the lower bound after conversion, ERROR LED will flash. ѓ ѓ Write the output settings of D100 and D101 into CR#6 and CR#7. The analog output will change with the changes in D100 and D101. Example 2:

Set the OFFSET value of CH2 as 2mA (= K400 LSB ) and GAIN value as18mA (= K3,600 LSB ). Example 1: Set the OFFSET value of CH1as 0V (= K0 LSB ) and GAIN value as 2.5V (= K1,000 LSB ). K1 M1000 D0 M0 K0 K1 D0 CMP H6401 ѓ D100 = K4000 D101 ѓ When D100 and D101 reach K4,000, they will be cleared as 0. FROM = K4000 M1 ѓ D100 increases K1 and D101 increases K5 every second. H10 K1 K1 H0 K1 K1 K1 K1 K1 K18 K0 K1000 K24 H18 K33 K33 K19 K25 M1013 4.2 Program Example K1 K1 K1 K1 K1 M1 TO TO TO TO TO ™ Program Example M1002 X0 M1002 Please note that: GAIN value – OFFSET value = +400 LSB ~ +6,000 LSB (voltage or current).

When GAIN – OFFSET is small (steep oblique), the resolution of output signal will be finer and variation on the digital value will be greater. When GAIN – OFFSET is big (gradual oblique), the resolution of output signal will be rougher and variation on the digital value will be smaller. Note: Each error status is determined by the corresponding bit (b0 ~ b7) and there may be more than 2 errors occurring at the same time. 0 = normal; 1 = error 9. CR#32: The setting of RS-485 communication speed. b0: 4,800bps; b1: 9,600bps (default); b2: 19,200bps; b3: 38,400bps; b4: 57,600bps; b5: 115,200bps; b6 ~ b13: reserved; b14: high/low bit exchange of CRC checksum (only valid in RTU mode); b15 = 0:

ASCII mode; b15 = 1: RTU mode. ASCII data format: 7-bit, Even bit, 1 stop bit (7, E, 1); RTU data format: 8-bit, Even bit, 1 stop bit (8, E, 1). 10. CR#33: For authorizations on some internal functions, e.g. OFFSET/GAIN tuning. The latched function will store the output setting in the internal memory before the power is cut off. 13. CR#0 ~ CR#34: The corresponding parameter addresses H’4032 ~ H’4054 are for users to read/write data by RS-485 communication. When using RS-485, the user has to separate the module with MPU first. b. Modbus ASCII/RTU communication protocols: ASCII data format (7-bit, Even bit, 1 stop bit (7, E, 1)); RTU data format (8-bit, Even bit, 1 stop bit (8, E, 1)). c.

Function: H’03 (read register data); H’06 (write 1 word datum to register); H’10 (write many word data to register) d. Latched CR should be written by RS-485 communication to stay latched. CR will not be latched if written by MPU through TO/DTO instruction. GAIN The voltage output value when the digital input value = K2,000 Range: -4V ~ +20V (-1,600 LSB ~ +8,000 LSB ) OFFSET The voltage output value when the digital input value = K0 Range: -5V ~ +5V (-2,000 LSB ~ +2,000 LSB ) GAIN - OFFSET Range: +1V ~ +15V (+400 LSB ~ +6,000 LSB ) GAIN - OFFSET Range:

+2mA ~ +30mA (+400 LSB ~ +6,000 Error status Content b15 ~ b8 b7 b6 b5 b4 b3 b2 b1 b0 Abnormal power supply K1(H’1) 0 0 0 0 0 0 0 1 Incorrect analog input value K2(H’2) 0 0 0 0 0 0 1 0 Incorrect mode setting K4(H’4) 0 0 0 0 0 1 0 0 OFFSET/GAIN error K8(H’8) 0 0 0 0 1 0 0 0 Hardware malfunction K16(H’10) 0 0 0 1 0 0 0 0 Abnormal digital range K32(H’20) 0 0 1 0 0 0 0 0 Incorrect average times setting K64(H’40) 0 1 0 0 0 0 0 0 1 0 0 0 0 0 0 0 The current output value when the digital input value = K2,000 Range: -8mA ~ +40mA (-1,600 LSB ~ +8,000 LSB ) The current output value when the digital input value = K0 Range: -10mA ~ +10mA (-2,000 LSB ~ +2,000 LSB ) 8. CR#31:

The setting of RS-485 communication address (Range: 01 ~ 255, default = K1). CR#1 mode 0 GAIN = 5V (2,000 LSB ) OFFSET = 0V (0 LSB ) CR#1 mode 1 GAIN = 6V (2,400 LSB ) OFFSET = 2V (800 LSB ) CR#1 mode 2 GAIN = 12mA (2,400 LSB ) OFFSET = 4mA (800 LSB ) CR#1 mode 3 GAIN = 10mA (2,000 LSB ) OFFSET = 0mA (0 LSB ) a. Communication baud rate: 4,800/9,600/19,200/38,400/57,600/115,200bps The adjustable range of voltage: -4V ~ +20V (-1,600 LSB ~ +8,000 LSB ) The adjustable range of current: -8 mA ~ +40 mA (-1,600 LSB ~ +8,000 LSB ) LSB ) [ Adjusting D/A Conversion Curve GAIN OFFSET 7. CR #30: Error status value (See the table below) reserved Voltage Output Mode Current Output Mode 12. CR#35 ~ CR#48: