ѓ ENGLISH ѓ Thank you for choosing Delta’s DVP series PLC. DVP04TC-E2 temperature measurement module receives 4 points of external thermocouple temperature sensors (J-type, K-type, R-type, S-type, T-type, E-type, N-type, ± 80mV) and convert them into 16-bit digital signals. Users can select temperatures in Celsius (resolution: 0.1°C) or Fahrenheit (resolution: 0.1°F). In addition, you can access the data in the module by applying FROM/TO instructions or read the average value of channels directly by using MOV instruction (Please refer to allocation of special registers D9900 ~ D9999). EN a DVP04TC-E2 is an OPEN-TYPE device.

It should be installed in a control cabinet free of airborne dust, humidity, electric shock and vibration. To prevent non-maintenance staff from operating DVP04TC-E2, or to prevent an accident from damaging DVP04TC-E2, the control cabinet in which DVP04TC-E2 is installed should be equipped with a safeguard. For example, the control cabinet in which DVP04TC-E2 is installed can be unlocked with a special tool or key. EN a DO NOT connect AC power to any of I/O terminals, otherwise serious damage may occur. Please check all wiring again before DVP04TC-E2 is powered up. After DVP04TC-E2 is disconnected, Do NOT touch any terminals in a minute.

Make sure that the ground terminal on DVP04TC-E2 is correctly grounded in order to prevent electromagnetic interference. FR a DVP04TC-E2 est un module OUVERT. Il doit ktre installй que dans une enceinte protectrice (boitier, armoire, etc.) saine, dйpourvue de poussiиre, d’humiditй, de vibrations et hors d’atteinte des chocs йlectriques. La protection doit йviter que les personnes non habilitйes а la maintenance puissent accйder а l’appareil (par exemple, une clй ou un outil doivent ktre nйcessaire pour ouvrir a protection). FR a Ne pas appliquer la tension secteur sur les bornes d’entrйes/Sorties, ou l’appareil DVP04TC-E2 pourra ktre endommagй.

Merci de vйrifier encore une fois le cвblage avant la mise sous tension du DVP04TC-E2. Lors de la dйconnection de l’appareil, ne pas toucher les connecteurs dans la minute suivante. Vйrifier que la terre est bien reliйe au connecteur de terre afin d’йviter toute interfйrence йlectromagnйtique. ѓ Product Profile & Dimension Removable I/O terminal Model Name Power / A->D / Error indicators I/O module connection port Mounting slot (35mm) I/O module clip [ Figure 1 ] I/O module connection port I/O terminal No. Direct mounting hole - 1 - Power 044ATI-CT-CE2 044ATI-CT-CE2

Стр. 2

61.5 Unit: mm ѓ External Wiring [ Figure 2 ] 78 Thermocouple Terminal of power module Note 1: Wiring for analog input should adopt the connection cable or shielding cable of thermocouple temperature sensor J-type, K-type, R-type, S-type, T-type, E-type and N-type and should be separated from other power cable or wirings that may cause interference. Note 2: Connect the terminal on both power module and DVP04TC-E2 to the system grounding point then ground the point or connect it to the cover of power distribution cabinet.

ѓ I/O Terminal Layout FE 1 2 3 4 5 6 7 8 9 10 11 12 FE FE FE 0V 24V DVP04TC-E2 (4AI) 1 2 3 4 5 6 7 8 FE FE ѓ Electrical Specifications - 2 - 62 70 90 98 106 110 Shielded cable *1 CH1 + I - I e input Shielded ~80mV cable *1 CH4 I I f e S*2 ystem 2 grounding rounding (100 Ω or less) 1+ MUX 1 - FE 4+ 4 - FE Cold-Junction Compensation 4V DC/ DC 5V 0V Converter AG I1+ I1- FE I2+ I2- FE I3+ I3- FE I4 + I4- DVP04TC-E2 Power supply voltage 24VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%) Max. rated power consumption 1.2W, supplied by external power source Connector European standard removable terminal block (Pin pitch: 5mm) Operation/storage Operation:

0°C~55°C (temp.), 5~95% (humidity), Pollution degree2 Storage: -25°C~70°C (temp.), 5~95% (humidity) Vibration/shock immunity International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/ IEC61131-2 & IEC 68-2-27 (TEST Ea) Series connection to The modules are numbered from 0 to 7 automatically by their distance

Стр. 3

ѓ Functions Specifications ѓ Control Register - 3 - DVP-PLC MPU from MPU. No.0 is the closest to MPU and No.7 is the furthest. Maximum 8 modules are allowed to connect to MPU and will not occupy any digital I/O points. Voltage DVP04TC-E2 Celsius (°C) Fahrenheit (°F) input Analog input channel 4 channels Digital data format 2’s complement of 16 bits Response time 200ms / each channel ±0.3% when in full scale (25°C, 77°F) ±0.6% when in full scale within the range of 0 ~ 55°C, 32 ~ 131°F Overall accuracy Applicable sensor J-type, K-type, R-type, S-type, T-type, E-type, N-type thermocouple; ±80mV voltage input type J-type: -100°C ~1,150°C K-type: -100°C ~ 1,350°C R-type: 0°C ~ 1,750°C S-type:

0°C ~ 1,750°C T-type: -150°C ~ 390°C E-type: -150°C ~ 980°C N-type: -150°C ~ 1,280°C J-type: -148°F ~ 2,102°F K-type: -148°F ~ 2,462°F R-type: 32°F ~ 3,182°F S-type: 32°F ~ 3,182°F T-type: -238°F ~734°F E-type: -238°F ~ 1,796°F N-type: -238°F ~2,336°F ±80mV Range of input J-type: K-1,000 ~ K11,500 K- type: K-1,000 ~ K13,500 R-type: K-0 ~ K17,500 S-type: K0 ~ K17,500 T-type: K-1,500 ~ K3,900 E-type: K-1,500 ~ K9,800 N-type: K-1,500 ~ K12,800 J-type: K-1,480 ~ K21,020 K-type: K-1,480 ~ K24,620 R-type: K320 ~ K31,820 S-type: K320 ~ K31,820 T-type: K-2,380 ~ K7,340 E-type: K-2,380 ~ K17,960 N-type:

K-2,380 ~ K23,360 ±8,000 Range of digital conversion 16 bits (0.1°C) 16bits (0.1°F) 16 bits (0.01mV) Resolution Supported. Available for setting up sampling range in CR#8 ~ CR#11. Range: K1 ~ K100. Average function Self-diagnosis Upper and lower bound detection in all channels Optical coupler isolation between digital circuits and analog circuits. Isolation between analog channels. 500VDC between digital circuits and Ground 500VDC between analog circuits and Ground 500VDC between analog circuits and digital circuits 500VDC between 24VDC and Ground 120VAC between analog channels Isolation CR# Attrib. Register content Description #0 O R Model name Set up by the system:

DVP04TC-E2 model code = H’0083 #1 O R Firmware version Display the current firmware version in hex. #2 O R/W CH1 Input mode setting Input mode: Default = H’0000. Take CH1 for example: Mode 0 (H’0000): J-type (-100°C ~1,150°C) Mode 1 (H’0001): K-type (-100°C ~ 1,350°C) Mode 2 (H’0002): R-type (0°C ~ 1,750°C) Mode 3 (H’0003): S-type (0°C ~ 1,750°C) Mode 4 (H’0004): T-type (-150°C ~ 390°C) Mode 5 (H’0005): E-type (-150°C ~ 980°C) #3 O R/W CH2 Input mode setting #4 O R/W CH3 Input mode setting

Стр. 4

- 4 - CR# Attrib. Register content Description #5 O R/W CH4 Input mode setting Mode 6 (H’0006): N-type (-150°C ~ 1,280°C) Mode 7 (H’0007): -80mV~+80mV Mode -1(H’FFFF): Close #7 O R/W Temperature unit setting Select the temperature unit (Celsius °C / Fahrenheit °F). Default = H0(°C) #8 O R/W CH1 sampling range Set sampling range at CH1 ~ CH4 Range = K1 ~ K100 Default = K10 #9 O R/W CH2 sampling range #10 O R/W CH3 sampling range #11 O R/W CH4 sampling range #12 X R Average temperature measured at CH1 Average temperature measured at CH1 ~ Ch2 Temperature unit:

set in CR#7 #13 X R Average temperature measured at CH2 #14 X R Average temperature measured at CH3 Average temperature measured at CH3 ~ Ch4 Temperature unit: set in CR#7 #15 X R Average temperature measured at CH4 #20 X R Present temperature measured at CH1 Present temperature measured at CH1 ~ CH4 Temperature unit: set in CR#7 #21 X R Present temperature measured at CH2 #22 X R Present temperature measured at CH3 #23 X R Present temperature measured at CH4 #28 O R/W Adjusted Offset value of CH1 Set the adjusted Offset value of Ch1 ~ Ch4. Default = K0 Range: K-400 ~ K400 Temperature unit: set in CR#7 Definition of Offset at Ch1 ~ Ch4 in DVP04TC-E2:

Deviation digital value from the target value. #29 O R/W Adjusted Offset value of CH2 #30 O R/W Adjusted Offset value of CH3 #31 O R/W Adjusted Offset value of CH4 #40 O R/W Function: Set value changing prohibited Prohibit set value changing in CH1 ~ CH4 #41 X R/W Function: Save all the set values Save all the set values, Default =H’0000 #42 X R/W Function: Return to default setting Set all values to default setting, Default = H’0000 #43 X R Error status Register for storing all error status. See the table of error status for more information. #100 O R/W Function: Enable / Disable limit detection Enable / Disable the upper and lower bound detection function. Default= H’0000.

#101 X R/W Upper and lower bound status Display the upper and lower bound value, Default =H’0000 #102 O R/W Set value of CH1 upper bound Set value of CH1~CH4 upper bound. Default = K32000. #103 O R/W Set value of CH2 upper bound #104 O R/W Set value of CH3 upper bound #105 O R/W Set value of CH4 upper bound #108 O R/W Set value of CH1 lower bound Set value of CH1~CH4 lower bound. Default = K-32000. #109 O R/W Set value of CH2 lower bound #110 O R/W Set value of CH3 lower bound #111 O R/W Set value of CH4 lower bound