ENGLISH Thank you for choosing Delta RTU-DNET DeviceNet Remote I/O Communication Module. RTU-DNET is applicable to the connection between the DeviceNet network and DVP-S (Slim) series DI/DO and AI/AO and offers status diagnosis for DI/DO and AI/AO EN RTU-DNET is an OPEN-TYPE device. It should be installed in a control cabinet free of airborne dust, humidity, electric shock and vibration. To prevent non-maintenance staff from operating RTU-DNET, or to prevent an accident from damaging RTU-DNET, the control cabinet in which RTU-DNET is installed should be equipped with a safeguard. For example, the control cabinet in which RTU-DNET is installed can be unlocked with a special tool or key.

EN DO NOT connect AC power to any of I/O terminals, otherwise serious damage may occur. Please check all wiring again before RTU-DNET is powered up. After RTU-DNET is disconnected, Do NOT touch any terminals in a minute. Make sure that the ground terminal on RTU-DNET is correctly grounded in order to prevent electromagnetic interference. FR RTU-DNET est un module OUVERT. Il doit ktre installй que dans une enceinte protectrice (boitier, armoire, etc.) saine, dйpourvue de poussiиre, d’humiditй, de vibrations et hors d’atteinte des chocs йlectriques.

La protection doit йviter que les personnes non habilitйes а la maintenance puissent accйder а l’appareil (par exemple, une clй ou un outil doivent ktre nйcessaire pour ouvrir a protection). FR Ne pas appliquer la tension secteur sur les bornes d’entrйes/Sorties, ou l’appareil RTU-DNET pourra ktre endommagй. Merci de vйrifier encore une fois le cвblage avant la mise sous tension du RTU-DNET. Lors de la dйconnection de l’appareil, ne pas toucher les connecteurs dans la minute suivante. Vйrifier que la terre est bien reliйe au connecteur de terre afin d’йviter toute interfйrence йlectromagnйtique. Features 1. Supports Group 2 only servers. 2.

Supports explicit connection in the pre-defined master/slave connection group and polled I/O connection. 3. The DeviceNet configuration software DeviceNet Builder provides graphic configuration interface to auto-scan and identify extension modules, configure control registers (CR) to be I/O data, set up error correction methods and diagnose errors in each module. 4. Users can determine whether to keep the data in the register when the network is cut off. 5. Extendable to max. 128 input points and 128 output points and connectable to 8 modules. 6. Supports Modbus protocol and connectable to 8 Modbus devices.

Product Profile & Dimensions 5 8 6 7 4 x 10 2 9 13 3 RTU-DNET IN 0 IN 1 DR 1 DR 0 x 10 11 1 10 12 [ Figure 1 ] - 1 -

Стр. 2

1. Extension I/O interface 8. RUN indicator 3. Function setup switch 10. DeviceNet port 2. Address setup switch 9. ALARM indicator 4. RUN/STOP switch 11. DIN rail 5. POWER indicator 12. DIN rail clip 6. MS (Module Status) indicator 13. RS-485 port Specifications 7.

NS (Network Status) indicator Power Supply DeviceNet Port DeviceNet Communication RS-485 Interface Electrical Specification Installation Dimensions - 2 - F or RTU-DNET Supplied by external power supply, 24 VDC, 60 mA F or DeviceNet Supplied by DeviceNet, 24 VDC, 60 mA C ommunication metho d CAN E lectrical isolation 500 VDC T ype Removable, 5.08 mm C ommunication cable 2 communication cables, 2 power cables, 1 shielded cable M essage type I/O polled, explicit Baudrate Standard mode: 125k, 250k, 500k bps Extended mode:

10k, 20k, 50k, 125k, 250k, 500k, 800k, 1M bps C ommunication speed 2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 115,200 bps Communication protocol ASCII ASCII/RTU ASCII ASCII/RTU ASCII ASCII/RTU ASCII ASCII/RTU C ommunication cable Shielded twisted pair cable Interference immunity ESD (IEC 61131-2, IEC 61000-4-2): 8 kV Air Discharge EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2 kV, Digital I/O: 1 kV Analog & Communication I/O: 1 kV Damped-Oscillatory Wave: Power Line: 1 kV, Digital I/O: 1 kV RS (IEC 61131-2, IEC 61000-4-3): 26 MHz ~ 1 GHz, 10 V/m Operation/storage Operation: 0°C ~ 55°C (temperature), 5 ~ 95% (humidity), pollution degree 2 Storage:

-25°C ~ 70°C (temperature), 5 ~ 95% (humidity) S i hock/vibration International standard: IEC 61131-2、IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27 (TEST Ea) mmunity S tandards IEC 61131-2, UL508

Стр. 3

DR 1 DR 0 x10 x10 RTU-DNET IN 0 IN 1 Unit: mm [ Figure 2 ] Connecting RTU-DNET to DVP-S Series Extension Modules RTU-DNET DVP-16SP DVP-02DA [ Figure 3 ] DeviceNet Port To connect to the DeviceNet network, use the DeviceNet port on RTU-DNET. 1 2 3 4 5 RUN/STOP Switch RUN STOP Address Setup Switch 2 3 4 1 5 0 6 9 8 7 2 3 4 1 5 0 6 9 8 7 The address setup switches x10 0 and x10 1 set up the node address on the DeviceNet network in decimal form. Range of settings: 00 ~ 63 (64 ~ 99 are forbidden) Example: If you need to set the node address of RTU-DNET to 26, switch the corresponding switch of x10 1 to 2 and the corresponding switch of x10 0 to 6.

- 3 - IN S ignal Color Descrip 1 2 C V- AN L _ Black 0 VD Blue Signa 3 SH IELD -- Shielded 4 C AN H _ White Signal 5 V+ Red 24 VD Action Explanation OP → RUN 1. Re-detecting the extension modules 2. Reading/writing the data in the extension module N → STOP Stop reading/writing the data in the extension module Settings Description 00 ~ 63 Valid DeviceNet node addresses 64 ~ 99 Invalid DeviceNet node addresses