ѓ ENGLISH ѓ Thank you for choosing Delta’s DVP series PLC. Delta releases DVP02LC-SL load cell module of weight measurement function. DVP02LC-SL provides 24-bit resolution applicable for 4-wire or 6-wire load cells with various eigenvalues. Therefore, the response time can be adjusted in coordination with each other according to users’ needs. On this basis, the market requirements on weight measurement can easily be met. EN a DVP02LC-SL is an OPEN-TYPE device. It should be installed in a control cabinet free of airborne dust, humidity, electric shock and vibration.
To prevent non-maintenance staff from operating DVP02LC-SL, or to prevent an accident from damaging DVP02LC-SL, the control cabinet in which DVP02LC-SL is installed should be equipped with a safeguard. For example, the control cabinet in which DVP02LC-SL is installed can be unlocked with a special tool or key. EN a DO NOT connect AC power to any of I/O terminals, otherwise serious damage may occur. Please check all wiring again before DVP02LC-SL is powered up. After DVP02LC-SL is disconnected, Do NOT touch any terminals in a minute. Make sure that the ground terminal on DVP02LC-SL is correctly grounded in order to prevent electromagnetic interference. FR a DVP02LC-SL est un module OUVERT.
Il doit ktre installй que dans une enceinte protectrice (boitier, armoire, etc.) saine, dйpourvue de poussiиre, d’humiditй, de vibrations et hors d’atteinte des chocs йlectriques. La protection doit йviter que les personnes non habilitйes а la maintenance puissent accйder а l’appareil (par exemple, une clй ou un outil doivent ktre nйcessaire pour ouvrir a protection). FR a Ne pas appliquer la tension secteur sur les bornes d’entrйes/Sorties, ou l’appareil DVP02LC-SL pourra ktre endommagй. Merci de vйrifier encore une fois le cвblage avant la mise sous tension du DVP02LC-SL. Lors de la dйconnection de l’appareil, ne pas toucher les connecteurs dans la minute suivante.
Vйrifier que la terre est bien reliйe au connecteur de terre afin d’йviter toute interfйrence йlectromagnйtique. ѓ Product Profile & Dimensions 3 mm DVP02LC ERR OR L.V POW ER R UN C H1 SEN+ SIG- SIG+ EXC+ EXC- M OTION M AX ZER O N ET SEN- SHD 90 mm EXC+ EXC- 1. Mounting hole of the I/O module 2. DIN rail mounting slot (35mm) 3. I/O module connection port 4. I/O module clip 5. Status indicator (POWER, RUN, ERROR and L.V) 6. Function status indicator (NET, ZERO, MAX, MOTION) 7. I/O terminals 8. RS-232 port 11. DC power input 9. Mounting slot clip 10. RS-485 port - 1 - SIG+ C H2SIG- N ET SEN+ ZER O SEN- M AX SHD M OTION 60 mm 33 m m [ Figure 1 ]
ѓ I/O Terminal Layout DVP02LC-SL CH1 CH2 ѓ External Wiring 4 strain guage EXC+ EXC- SIG+ A+5V AGND SEN+ SIG- CH1 6 strain guage EXC+ SEN- A+5V EXC- SIG+ SIG- AGND SEN+ SEN- CH2 Terminal of power module System grounding *1 A+5V Grounding [ Figure 2 ] (100 or less) AGND Note 1: Please connect the terminal on both the power module and Load Cell module to the system earth point and ground the system contact or connect it to the cover of power distribution cabinet.
ѓ Electrical Specifications - 2 - EXC+ EXC- SIG + SIG- SE N+ SEN- SHD EX C+EXC- SIG+ SIG- SEN + SEN- SHD 0V DC/DC Converter Load cell module Voltage output Rated power supply voltage/ 24 VDC (-15 to +20%) / 3W power consumption Voltage Boundary 18 to 31.2 VDC Max. current consumption 125 mA Input signal range ± 40 mVDC Sensibility +5 VDC +/-10% Internal resolution 24 bits Communication port RS-232, RS-485 Applicable sensor type 4-wire or 6-wire strain gauge Temperature coefficient span ≤ ± 50 ppm/K v. E Temperature coefficient zero ≤ ± 0.4 μV/K point Linearity error ≤ 0.02% Response time 2, 10, 20, 40, 80 ms × channels 4 measuring ranges 0 to 1 mV/V, 0 to 2 mV/V, 0 to 4 mV/V, 0 to 6mV/V Max.
distance for connecting 100 M to load cell Max. current output 5 VDC * 300 mA Permitted load cell resistance 40 to 4,010 Ω
™ Complying with DIN1319-1, the tolerance of measured value should be ≤ 0.05% under 20°C + 10K temperature range . ™ When the corrected ambient temperature and the actual temperature have a difference of more than 10°C, it is suggested that you re-correct it. ѓ Control Register - 3 - Load cell module Voltage output Common mode rejection ≥100dB (CMRR @50/60 Hz) Dynamic value filter Setting range: K1 to K5 Average value filter Setting range:
K1 to K100 500 VAC between digital circuits and Ground 500 VAC between analog circuits and Ground 500 VAC between analog circuits and digital circuits Isolation method Connectable to the left side of MPU, numbered from 100 to 107 according to the position of module from the closest to farthest to MPU. Series connection to DVP-PLC MPU Operation: 0 to 55°C (temp.), 5 to 95% (humidity), pollution degree 2 Storage: -25 to 70°C (temp.), 5 to 95% (humidity) Operation / storage temperature International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/ IEC61131-2 & IEC 68-2-27 (TEST Ea) Vibration / shock immunity CR# Add. Attrib. Register name Explanation #0 H1000 O R Model name Set up by the system:
DVP02LC-SL model code = H’4206 #1 H1001 O R Firmware version Display the current firmware version in hex. #2 H1002 O R/W Characteristic value Mode 0 (H’0000): 1 mV/V Mode 1 (H’0001): 2 mV/V, default Mode 2 (H’0002): 4 mV/V Mode 3 (H’0003): 6 mV/V #3 H1003 O R/W Reaction time for measurement Mode 0 (H’0000): 2 ms Mode 1 (H’0001): 10 ms Mode 2 (H’0002): 20 ms Mode 3 (H’0003): 40 ms Mode 4 (H’0004): 80 ms, default #4 H1004 O R Average value of all channels Sum up CH1 average value and CH2 average value and equalize them. Equation: (CH1 average value + CH2 average value)/2 #6 H1006 X R/W CH1 to CH2 read tare weight Read present average value as tare weight value bit0: CH1; bit1:
CH2; bit2 to bit15: reserved #7 H1007 O R/W CH1 to CH2 gross/net weight Display present weight as Gross (K0) or Net (K1). bit0 to bit3: CH1; bit4 to bit7: CH2; bit8 to bit15: reserved. Take CH1 for example: bit3 to bit0 = 0000, gross; bit3 to bit0 = 0001, net; bit3 to bit0 = 1111, channel disabled. #8 H1008 O R/W CH1 tare weight The user can write in the weight or read it by commands. Default: K0; Range: -K32,768 to K32,767. #9 H1009 O R/W CH2 tare weight #10 H100A O R/W CH1 average times Default: K10; Range: K1 to K100. When the set value exceeds the range, it will automatically be changed to K1 or K100. #11 H100B O R/W CH2 average times
- 4 - CR# Add. Attrib. Register name Explanation #12 H100C X R CH1 average weight Display average weight. #13 H100D X R CH2 average weight #14 H100E X R CH1 present weight Display present weight. #15 H100F X R CH2 present weight #16 H1010 O R/W CH1 standstill times Default: K5 Range: K1 to K500 #17 H1011 O R/W CH2 standstill times #18 H1012 O R/W CH1 standstill range Default: K10 Range: K1 to K10,000 #19 H1013 O R/W CH2 standstill range #20 H1014 O R/W CH1 decimal place Default: K2 Range: K1 to K4 #21 H1015 O R/W CH2 decimal place #22 H1016 O R/W CH1 unit of measurement Enter max. 4 ASCII words. CR#22, CR#24: High word CR#23, CR#25:
Low word #23 H1017 O R/W CH1 unit of measurement #24 H1018 O R/W CH2 unit of measurement #25 H1019 O R/W CH2 unit of measurement #26 H101A X R/W Weight correction command For the user to correct the weight. Default: H’0000 H’0001: CH1 Reset to zero command H’0002: CH1 Weight base point command H’0003: CH2 Reset to zero command H’0004: CH2 Weight base point command (Please use CR#41 to make the correction parameter retentive after finishing correcting the weight.) #33 H1021 O R/W CH1 weight base point For CR#33 to CR#34 default = K1,000; Range: K-32,768 to K32,767 Steps for correction: Take CH1 for example 1: Place no weights on the load cell 2: Set up CR#26 command = “H’0001” 3:
Place standard weights on load cell 4: Write the weight of the weights on the plate into CR#33. 5: Set up CR#26 command = “H’0002” #34 H1022 O R/W CH2 weight base point #35 H1023 O R CH1 max. weight Set up the max. weight. When the measured value exceeds the set value, error codes will be recorded. #36 H1024 O R CH2 max. weight #37 H1025 O R/W Upper limit for CH1 zero point check Reference for reset to zero. When the weight is within this range, the status code will be set to “zero bit”, indicating the current zero weight status. Default: K10 Range:
K-32,768 to K32,767 #38 H1026 O R/W Upper limit for CH2 zero point check #39 H1027 O R/W Lower limit for CH1 zero point check Reference for reset to zero. When the weight is within this range, the status code will be set to “zero bit”, indicating the current zero weight status. Default: K-10 Range: K-32,768 to K32,767 #40 H1028 O R/W Lower limit for CH2 zero point check