2014-01-22 5012617003-X203
ѓ ENGLISH ѓ Thank you for choosing Delta’s DVP-EX2 series PLC. DVP-EX2 series provides 30 points MPU (16 points digital Input, 10 points digital Output, 3 channel Analog input and 1 channel Analog output). The maximum I/O points including those on the MPU are 256 points. DVP-EX2 series PLCs satisfy various applications in that they can be used with analog input/output modules. Users do not have to install any batteries in DVP-EX2 series PLCs. The PLC programs and the latched data are stored in the high-speed flash memories. EN a DVP30EX2 is an OPEN-TYPE device. It should be installed in a control cabinet free of airborne dust, humidity, electric shock and vibration.
To prevent non-maintenance staff from operating DVP30EX2, or to prevent an accident from damaging DVP30EX2, the control cabinet in which DVP30EX2 is installed should be equipped with a safeguard. For example, the control cabinet in which DVP30EX2 is installed can be unlocked with a special tool or key. EN a DO NOT connect AC power to any of I/O terminals, otherwise serious damage may occur. Please check all wiring again before DVP30EX2 is powered up. After DVP30EX2 is disconnected, Do NOT touch any terminals in a minute. Make sure that the ground terminal on DVP30EX2 is correctly grounded in order to prevent electromagnetic interference. FR a DVP30EX2 est un module OUVERT.
Il doit ktre installй que dans une enceinte protectrice (boitier, armoire, etc.) saine, dйpourvue de poussiиre, d’humiditй, de vibrations et hors d’atteinte des chocs йlectriques. La protection doit йviter que les personnes non habilitйes а la maintenance puissent accйder а l’appareil (par exemple, une clй ou un outil doivent ktre nйcessaire pour ouvrir a protection). FR a Ne pas appliquer la tension secteur sur les bornes d’entrйes/Sorties, ou l’appareil DVP30EX2 pourra ktre endommagй. Merci de vйrifier encore une fois le cвblage avant la mise sous tension du DVP30EX2. Lors de la dйconnection de l’appareil, ne pas toucher les connecteurs dans la minute suivante.
Vйrifier que la terre est bien reliйe au connecteur de terre afin d’йviter toute interfйrence йlectromagnйtique. ѓ Product Profile & Dimension POWER, RUN ERROR indicators , & COM I/O point indicators COM1 Communication (RS-232C) port Run/Stop switch I/O terminal No. I/O module port connection I/O terminal No. DVP30EX2 16 DI/10 DO/3AI/1AO Output type R Mounting slot (35mm) COM2/COM3 (RS-485) Model Name I/O module clip DIN rail clip Removable I/O terminal block Direct mounting hole [ Figure 1 ] 90 98 106 110 Unit: mm 157 165 [ Figure 2 ] 78 61.5 - 1 -
ѓ Electrical Specifications #1: UP, ZP must work with external auxiliary power supply 24VDC (-15% ~ +20%), rated consumption approx. 1mA/point. - 2 - Mode l DVP30EX200R DVP30EX200T Item Power supply 100 ~ 240VAC (-15% ~ 10%), 50/60Hz ±5% voltage Connector European standard removable terminal block (Pin pitch: 5mm) DVP-EX2 starts to run when the power rises to 95 ~ 100VAC and stops when the power drops to 70VAC. If the power is suddenly cut off, the MPU will continue running for 10ms.
Operation Power supply fuse 2A/250VAC Power 30VA consumption DC24V current 500mA output Power supply DC24V output short circuit protection protection 1,500VAC (Primary-secondary), 1,500VAC (Primary-PE), 500VAC (Secondary-PE) Voltage withstand Insulation > 5MΩ at 500VDC (between all I/O points and ground) resistance ESD (IEC 61131-2, IEC 61000-4-2): 8kV Air Discharge EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2kV, Digital I/O: 1kV, Analog & Communication I/O: 1kV RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m Noise immunity The diameter of grounding wire shall not be less than that of L, N terminal of the power supply.
(When many PLCs are in use at the same time, please make sure every PLC is properly grounded.) Grounding Operation: 0°C~55°C (temperature), 5~95% (humidity), pollution degree 2 Storage: -25°C~70°C (temperature), 5~95% (humidity) Environment UL508 European community EMC Directive 89/336/EEC and Low Voltage Directive 73/23/EEC Agency approvals Vibration/shock International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/ IEC61131-2 & IEC 68-2-27 (TEST Ea) immunity Weight(g) 505 530 Input Point Input No. X0 ~ X3 X4 ~ X7 X10 ~ X17 Type Digital input Input type DC (SINK or SOURCE) Input current 24VDC, 5mA Input impedance 3.9KΩ 4.7KΩ Max.
frequency 100kHz 10kHz 60Hz Action level Off → On >15VDC On → Off Response time Off → On On → Off Filter time X0 ~ X7 Adjustable within 0 ~ 20ms in D1020 (Default: 10ms) Output Point Output point type Relay-R Transistor-T Output point number All Y0, Y2 Y1, Y3 Y4~Y11 Voltage specification 5 ~ 30VDC #1 Max. frequency 1Hz 100kHz 10kHz 1kHz Resistive 2A/1 point (5A/COM) 0.5A/1 point (4A/ZP) Maximum load Inductive #2 15W (30VDC) Lamp 20WDC/100WAC 2.5W(30VDC) Response time Off → On Approx .10ms On → Off
#2: Life curves 1,000 2,000 3,000 Operation(X10 ) 3 200 300 500 100 20 30 50 Current(A) [ Figure 3 ] ђ Specifications of A/D, D/A and Temperature Sensors 0.5 0.1 0.2 0.3 0.7 1 2 #1: Detailed explanation of D1115: (Default is HFFFF, disable all channels) A/D input mode: D/A output mode: For example: Assume A/D-Ch0 is PT100(3wire), A/D-Ch1 is PT100(2wire), A/D-Ch2 is 4mA~20mA and D/A is 4~20mA, then the D1115 will be set to H2C04. #2: Resolution formula #3: When the scan period is longer than 25ms, the setting will follow the scan period. #4: When the scan period is longer than 2ms, the setting will follow the scan period.
- 3 - 120V AC R esi stive ms) cosψ=0.4) 30VD C In duc tive(t=7 ms) 24 0VA C In ductive( cosψ=0.4) 12 0VA C Induc tive(cosψ=0.4) Contact 30V Ind DC uctive ( t=40m s) Analog Input (A/D) #1 Analog Output (D/A) #1 Items Voltage Current Voltage Current Analog I/O range ±10V ±5V 1~5V ±20mA 4~20mA ±10V 0~20mA 4~20mA Digital conversion ±32,000 0~32,000 ±32,00 0 0~32,000 ±32,000 0~32,000 range Resolution #2 16-bit 12-bit Input impedance > 1MΩ 250Ω - Output impedance - 0.5Ω or lower Tolerance carried - > 5KΩ impedance Response time 25m s #3 2ms #4 Absolute input ±15V ±32mA - range Average function Provided (set up in D1062) #5 - Temperature Sensor PT100 / PT1000 Input #1 NI100 / NI1000 Input #1 Temperature Range -180ºC ~ 800ºC -80ºC ~ 170ºC Digital conversion -1800 ~ 8000 -800 ~ 1700 range Resolution 20-bit Response time 3-Wire:
210ms/2-Wire: 105ms Average function Provided (set up in D1062) #5 Non-linear accuracy: ±1% of full scale within the range of PLC operation temperature Maximum deviation: ±1% of full scale at 20mA and +10V Overall accuracy Digital data format 2’s complement of 16-bit, 12 significant bits Isolation method No Isolation between digital circuit and analog circuit Voltage output has short circuit protection, but a long period of short circuit may cause internal wire damage and open circuit of current output.
Protection Bit15~12(D/A) Bit11~8(A/D-Ch2 ) Bit7~4(A/D-Ch1) Bit3~0(A/D-Ch0) D/A output mode A/D input mode A/D input mode A/D input mode Value 0 1 2 3 4 5 Mode PT100(2wire ) NI100(2wire) PT1000(2wire) NI1000(2wire) PT100(3wire) NI100(3wire) Value 6 7 8 9 A B Mode PT1000(3wir e) NI1000(3wire) -10V ~ +10V -5V ~ +5V +1V ~ +5V -20mA~+20mA Value C D E F Mode 4mA ~ 20mA Reserved Disabled Value 0 1 2 3~E F Mode -10V ~ +10V 0mA ~ 20mA 4mA ~ 20mA Reserved Disabled Analog Input (A/D) Analog Output (D/A) Voltage Current Voltage Current 20V (312.5μV= ) 64000 40mA (0.625μΑ= ) 64000 20V (5mV= ) 4000 20mA (5μΑ= ) 4000