ѓ ENGLISH ѓ Thank you for choosing Delta DVP series PLC. DVP06PT-S is able to receive 6 points of RTDs and convert them into 16-bit digital signals. Besides, through FROM/TO instructions in DVP Slim series MPU program, the data in DVP06PT-S can be read and written. There are many 16-bit control registers (CR) in DVP06PT-S. The power unit is separate from it and is small in size and easy to install. EN a DVP06PT-S is an OPEN-TYPE device. It should be installed in a control cabinet free of airborne dust, humidity, electric shock and vibration.
To prevent non-maintenance staff from operating DVP06PT-S, or to prevent an accident from damaging DVP06PT-S, the control cabinet in which DVP06PT-S is installed should be equipped with a safeguard. For example, the control cabinet in which EN a DO NOT connect AC power to any of I/O terminals, otherwise serious damage DVP06PT-S is installed can be unlocked with a special tool or key. may occur. Please check all wiring again before DVP06PT-S is powered up. After DVP06PT-S is disconnected, Do NOT touch any terminals in a minute. Make sure that the ground terminal on DVP06PT-S is correctly grounded in order to prevent electromagnetic interference. FR a DVP06PT-S est un module OUVERT.
Il doit ktre installй que dans une enceinte protectrice (boitier, armoire, etc.) saine, dйpourvue de poussiиre, d’humiditй, de vibrations et hors d’atteinte des chocs йlectriques. La protection doit йviter que les personnes non habilitйes а la maintenance puissent accйder а l’appareil (par exemple, une clй ou un outil doivent ktre nйcessaire pour ouvrir a protection). FR a Ne pas appliquer la tension secteur sur les bornes d’entrйes/Sorties, ou l’appareil DVP06PT-S pourra ktre endommagй. Merci de vйrifier encore une fois le cвblage avant la mise sous tension du DVP06PT-S. Lors de la dйconnection de l’appareil, ne pas toucher les connecteurs dans la minute suivante.
Vйrifier que la terre est йlectromagnйtique. bien reliйe au connecteur de terre afin d’йviter toute interfйrence ѓ Product Profile & Dimension 60.00 [ Figure 1 ] 1. Status indicator (POWER, RUN and ERROR) 2. Model name 3. DIN rail clip Unit: mm 4. I/O terminals 5. I/O point indicator 6. Mounting holes - 1 - 3.00 1 2 90.00 3 3.00 4 6 6 3.00 25.20 5 60.00 7 3.40 L LLLL LII I+ -+-- +-- -CH2CH1 8 12 10 CH3 11 LLLL LL III +--- ++ --- CH6CH5CH4 9 DVP-06PT 3 [
7. Specification label 8. I/O module connection port 9. I/O module clip 10. DIN rail (35mm) 11. I/O module clip 12. I/O module connection port ѓ I/O Terminal Layout ѓ External Wiring 3- wire PT100 Shielded cable*1 CH1 I- L- L+ 1.53mA AG 2- wire PT1000 Shielded cable*1 CH6 I- L- L+ 0.2048mA Note1: Use only the wires that are packed with the temperature sensor for analog input and separate from other power line or any wire that may cause noise. Note2: If there is noise, please connect the shielded cables to the system earth point, and then ground the system earth point or connect it to the distribution box. Note 3:
Please keep wires as short as possible when connecting the module to a device whose temperature is going to be measured, and keep the power cable used as far away from the cable connected to a load as possible to prevent noise interference. ѓ Electrical Specifications AG ѓ Functional Specifications - 2 - DVP06PT CH1 CH2 CH3 CH4 CH5 CH6 L+ L- I- L+ L- I- L+ L- I- L+ L- I- L+ L- I- L+ L- I- [ Figure 2 ] L+ L- I- L+ L- I- L+ L- I- L+ L- I- L+ L- I- L+ L- I- Max. rated power 2W consumption Operation: 0°C~55°C (temp.), 5~95% (humidity), pollution degree 2 Storage: -25°C~70°C (temp.), 5~95% (humidity) Operation/storage Vibration/shock International standards:
IEC61131-2, IEC 68-2-6 (TEST Fc)/ IEC61131-2 & IEC 68-2-27 (TEST Ea) resistance The modules are numbered from 0 to 7 automatically by their distance from MPU. No.0 is the closest to MPU and No.7 is the furthest. Maximum 8 modules are allowed to connect to MPU and will not occupy any digital I/O points. Series connection to DVP-PLC MPU DVP06PT-S Celsius (°C) Fahrenheit (°F) Analog input channel 6 channels per module 2-wire/3-wire PT100/ Ni100/ PT1000/ Ni100 3850 PPM/°C (DIN 43760 JIS C1604-1989) Sensors type Current excitation 1.53mA / 204.8uA Temperature input range Please refer to the temperature/digital value characteristic curve.
Digital conversion range Please refer to the temperature/digital value characteristic curve. Resolution 16 bits (0.1°C) 16 bits (0.1°F) Overall accuracy ±0.6% of full scale during 0 ~ 55°C (32 ~ 131°F) Response time 1 second Isolation between digital and analog circuitry. There is no isolation between channels. 500VDC between digital circuits and Ground 500VDC between analog circuits and Ground 500VDC between analog circuits and digital circuits 500VDC between 24VDC and Ground Isolation method Digital data format 2’s complement of 16-bit Average function Yes (CR#2) Self diagnostic function Every channel has the upper/lower limit detection function.
ѓ Control Register - 3 - CR# Save Register content Description #0 O R Model name Set up by the system: DVP06PT-S model code = H’CA #1 X R/W CH1~CH4 Mode setting CH1 mode: b0 ~ b3 CH2 mode: b4 ~ b7 CH3 mode: b8 ~ b11 CH4 mode: b12 ~ b15 Take CH1 mode (b3,b2,b1,b0) for example. The default value is H’0000. 1. (0,0,0,0): PT100 2. (0,0,0,1): NI100 3. (0,0,1,0): PT1000 4. (0,0,1,1): NI1000 5. (1,1,1,1): The channel is disabled. #2 X R/W CH1~CH6 average number Number piece of readings used for the calculation of “average” temperature on channels CH1 ~ CH6 Setting range: K1~K20. Default setting is K10. #6 X R CH1 average degrees Average degrees for channels CH1 ~ CH6 (Unit: 0.1°C).
#7 X R CH2 average degrees #8 X R CH3 average degrees #9 X R CH4 average degrees #10 X R CH5 average degrees #11 X R CH6 average degrees #12 X R CH1 average degrees Average degrees for channels CH1 ~ CH6 (Unit: 0.1°F). #13 X R CH2 average degrees #14 X R CH3 average degrees #15 X R CH4 average degrees #16 X R CH5 average degrees #17 X R CH6 average degrees #18 X R Present temp. of CH1 Present temperature of channels CH1 ~ CH6 (Unit: 0.1°C). #19 X R Present temp. of CH2 #20 X R Present temp. of CH3 #21 X R Present temp. of CH4 #22 X R Present temp. of CH5 #23 X R Present temp. of CH6 #24 X R Present temp. of CH1 Present temperature of channels CH1 ~ CH6. (Unit: 0.1°F). #25 X R Present temp.
of CH2 #26 X R Present temp. of CH3 #27 X R Present temp. of CH4 #28 X R Present temp. of CH5 #29 X R Present temp. of CH6 #30 X R Error status Data register stores the error status. Refer to the error code chart for details. #31 X R/W CH5~CH6 Mode setting CH5 mode: b0 ~ b3 CH6 mode: b4 ~ b7 Take CH5 mode (b3,b2,b1,b0) for example. The default value is H’0000. 1. (0,0,0,0): PT100 2. (0,0,0,1): NI100 3. (0,0,1,0): PT1000 4. (0,0,1,1): NI1000 5. (1,1,1,1): The channel is disabled. #32 X R/W CH5~CH6 Error LED indicator setting 1. b12 corresponds to CH5. When b12=1, the scale exceeds the range, and the Error LED indicator flashes. 2. b13 corresponds to CH6.
When b13=1, the scale exceeds the range, and the Error LED indicator flashes.
1. CR#30 is the error code register. Refer to the chart below: - 4 - CR# Save Register content Description #33 X R/W Reset to default setting CH1~CH4 Error LED indicator setting If b0~b11 are set to H’924, all the setting values will be reset to the default setting. 1. b12 corresponds to CH1: when b12=1, the scale exceeds the range, and the Error LED indicator flashes. 2. b13 corresponds to CH2: when b13=1, the scale exceeds the range, and the Error LED indicator flashes. 3. b14 corresponds to CH3: when b14=1, the scale exceeds the range, and the Error LED indicator flashes. 4. b15 corresponds to CH4: when b15=1, the scale exceeds the range, and the Error LED indicator flashes.
#34 O R Firmware version Display the firmware version in hexadecimal. ex: H’010A = version 1.0A #35 ~ #48 System used Error description Content b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 Power source abnormal K1 (H’1) 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 The contact is not connected to anything. K2 (H’2) 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 Hardware malfunction K16 (H’10) 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0 The contact of CH1 is not connected to anything. (Abnormal conversion) K256 (H’100) 0 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 The contact of CH2 is not connected to anything. (Abnormal conversion) K512 (H’200) 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 The contact of CH3 is not connected to anything.
(Abnormal conversion) K1024 (H’400) 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 The contact of CH4 is not connected to anything. (Abnormal conversion) K2048 (H’800) 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 The contact of CH5 is not connected to anything. (Abnormal conversion) K4096 (H’1000) 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 The contact of CH6 is not connected to anything. (Abnormal conversion) K8192 (H’2000) 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 Note: Each error code will have a corresponding bit. Two or more errors may happen at the same time. 0 means normal and 1 means having error.