Delta Electronics · 2 стр.
Installation & Wiring Guide: Delta DOP-107CV/DOP-107EV HMI (EN)
Оригинальное название: 5014093300-EN
Похожие инструкции
Содержание
Текст документа
5014093300-SC
Incorrect installation may result in malfunction. To ensure the HMI is well ventilated, make sure there is sufficient space between the HMI and the adjacent objects or walls. This product should be used on a case / platform which conforms to enclosure Type 4X standard (for indoor use only). The maximum panel thickness for mounting must be no greater than 5 mm. Step 2: Place the fasteners into the slots and tighten the screws until reaching the panel cutouts. Step 4: For heat dissipation, please keep a minimum clearance of 60 mm on the rear of the HMI.
Solid 24 – 12 7 – 8 mm 5 kg-cm (4.3 lb-in) Stranded 24 – 12 7 – 8 mm 5 kg-cm (4.3 lb-in) Please refer to the following diagram when wiring the power connector. The temperature rating of the cable must be greater than 75°C (167°F). Type Wire gauge (AWG) Stripped length Torque Step 1: Put the waterproof gasket into the HMI and then insert the HMI into the panel cutout. Step 3: Tighten the screws with the torque less than 0.5 N-M / 0.7 N-M to avoid damage to the plastic case. Torque for DOP-107CV / DOP-107EV: 6.17 lb-inch (0.7 N-M) (5) Installation and wiring Installation steps: Precautions: Wiring: Unit: mm (inch) Operation temperature: 0°C to 50°C (32°F to 122°F) Storage temperature:
-20°C to 60°C (-4°F to 140°F) (24AWG wire min.) B COM2/COM3 C COM1 D Only for DOP-107EV F A Power input terminal E Network port (LAN) (4) Mounting dimensions DOP-107CV / DOP-107EV Install the product in an indoor location, which is free of vapor, corrosive and inflammable gas and liquids. Please refer to the wiring diagram when connecting the wires. Ensure your HMI is correctly grounded. The grounding method must comply with the national electrical standard (please refer to NFPA 70: National Electrical Code, 2005 Ed.). Do not disassemble the HMI or change the wiring when power is on. Do not touch the power supply when power is on, or it may cause electric shock.
When the HMI displays a low power notification and requires a battery change, please contact your local distributor or Delta Customer Service Center for the replacement. Do not change the batteries by yourself. This product can be used with other industrial automation equipment. Please read through this sheet carefully and install the product according to the instructions to avoid danger. Cleaning method: please use a dry cloth to clean the product. This product must be used at an altitude below 2,000 m. If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
For repair and maintenance, please contact Delta Electronics, Inc. Address: No.18, Xinglong Rd., Taoyuan City, Taiwan. TEL: +886-3-3626301. If you have any inquiry during operation, please contact our local distributors or Delta sales representatives. The content of this instruction sheet may be revised without prior notice. Please consult our distributors or download the latest version at Delta’s website (http://www.delta.com.tw/ia). RS-232 RS-485 RS-485 RS-485 RS-232 RS-422 Thank you for purchasing this product. This instruction sheet provides information about the DOP-100 series HMI.
Before using this product, please read through this instruction sheet carefully to ensure the correct use of the product. Please keep this sheet handy for quick reference whenever needed. Before finishing reading this sheet, please follow the instructions below: COM2 COM3 COM2 COM3 COM2 COM3 1 - - D+ - - TXD+ 2 RXD - - - RXD - 3 TXD - - - TXD - 4 - D+ - D+ - RXD+ 6 - - D- - - TXD- 7 RTS - - - RTS - 8 CTS - - - CTS - 9 - D- - D- - RXD- High color ‧ Wide screen ‧ User-friendly Delta Electronics, Inc.
No.18, Xinglong Rd., Taoyuan City 33068, Taiwan MODE1 MODE2 MODE3 5 GND GND GND DOP-107EV DOP-107CV COM Port Pin MODE1 RS-232 1 - 2 RXD 3 TXD 4 - 5 GND 6 - 7 RTS 8 CTS 9 - Instruction Sheet (2) Communication port pin assignment Note: mark “-” means connection is not required.
(1) General precautions DOP-107CV / DOP-107EV COM1 DOP-107CV / DOP-107EV COM2 COM Port Pin A Operation / display area A Power input terminal B COM2/COM3 (24AWG wire min.) C COM1 COM1 D USB Host E Network port (LAN) F USB Slave Only for DOP-107EV MODE1 COM Port Pin RS-232 1 - 2 RXD 3 TXD 4 - 5 GND 6 - 7 RTS 8 CTS 9 - Type Wire gauge (AWG) Stripped length Torque Solid 24 – 12 7 – 8 mm Stranded 24 – 12 7 – 8 mm MODE1 MODE2 MODE3 COM Port Pin COM2 COM3 COM2 COM3 COM2 COM3 RS-232 RS-485 RS-485 RS-485 RS-232 RS-422 1 - - D+ - - TXD+ 2 RXD - - - RXD - 3 TXD - - - TXD - 4 - D+ - D+ - RXD+ 5 GND GND GND 6 - - D- - - TXD- 7 RTS - - - RTS - 8 CTS - - - CTS - 9 - D- - D- - RXD-
5014093300-SC
Backlight LED Back Light (half-life under room temperature 25°C > 20,000 hours) * 1 Network interface N/A 1 Port, 10 / 100 Mbps auto detection Approvals CE / UL (please use shielding network cable and magnetic ring with the Supplied by Class 2 or SELV circuit (isolated from MAINS by double insulation) Note: 1. The half-life of the backlight is defined as the maximum luminance being reduced by 50% when the maximum drive current is supplied to the HMI. The life of LED backlight shown here is estimated at the room temperature of 25°C with ambient humidity. 2. The withstand voltage of the isolated power circuit is 1500V peak for 1 minute. 3.
The HMI power consumption is the power consumed when the HMI is not connecting with other peripheral devices. To ensure normal operation of the HMI, the recommended capacity of the power supply is 1.5 to 2 times of the specified power consumption. 4. Isolated power supply is recommended. 5. For the DOPSoft programming software of the DOP-100 series and the user manual, you can download them at http://www.delta.com.tw/ia.
(built-in isolated circuit) *2 Operation voltage *2 DC +24V (-15% to +15%) (please use an isolated power supply) Leakage current 500 V AC for 1 minute (between DC24V terminal and FG terminal) Operating environment 10% to 90% RH [0°C - 40°C], 10% to 55% RH [41°C - 50°C]; Vibration resistance Conforms to IEC61131-2: continuous vibration 5 Hz - 8.3 Hz with 6. DOP-100 series can be used with other industrial automation equipment. Please read through this sheet carefully and install the product according to the instructions to avoid danger.
Model DOP-107CV DOP-107EV Touchscreen 4-wire resistive touchscreen > 10,000,000 operated Power consumption *2 8.5 W (Max) *3 8.76 W (Max) *3 (subject to operation temperature and condition) amplitude 3.5 mm; 8.3 Hz - 150 Hz with amplitude 1G 11 ms, 15 G Peak, in X, Y, Z directions each for 6 times Buzzer Multi-tone Frequency (2K – 4K Hz) / 80 dB USB 1 USB Slave Ver. 2.0; 1 USB Host Ver.
2.0 COM2 RS-232 (supporting flow control) / RS-485 *2 Panel type 7" TFT LCD (65535 colors) CPU ARM Cortex-A8 (800 MHz) COM1 RS-232 (supporting flow control) *2 filter of 300 ohm / 100 MHz) Backup battery 3V lithium battery CR2032 Ч 1 Backup battery life About 3 years or more at 25°C Operation temperature 0°C to 50°C (32°F to 122°F) Storage temperature -20°C to +60°C (-4°F to 140°F) Shock resistance Conforms to IEC60068-2-27: Resolution 800 x 480 pixels Display range 154.08 x 85.92 mm Brightness 400 cd / mІ (Typ.) COM3 RS-422 / RS-485 *2 Cooling method Natural cooling Panel waterproof level IP65 / NEMA4 pollution degree:
2 (W) x (H) x (D) mm 215 x 161 x 50 (W) x (H) mm 196.9 x 142.9 Weight Approx.
970 g Flash ROM 256 Mbytes RAM 256 Mbytes SD N/A Auxiliary function key N/A Calendar Built-in (6) Hardware specifications Mounting dimension Dimension communication Display Serial port Model DOP-107CV DOP-107EV Panel type 7" TFT LCD (65535 colors) Resolution 800 x 480 pixels Display Backlight LED Back Light (half-life under room temperature 25°C > 20,000 hours)*1 Display range 154.08 x 85.92 mm Brightness 400 cd / m² (Typ.) CPU ARM Cortex-A8 (800 MHz) Flash ROM 256 Mbytes RAM 256 Mbytes Touchscreen 4-wire resistive touchscreen > 10,000,000 operated Buzzer Multi-tone Frequency (2K – 4K Hz) / 80 dB 1 Port, 10 / 100 Mbps auto detection Network interface N/A (built-in isolated circuit)*2 USB 1 USB Slave Ver.
2.0; 1 USB Host Ver.
2.0 SD N/A RS-232 (supporting flow control)*2 COM1 Serial RS-232 (supporting flow control) / RS-485*2 communication COM2 port COM3 RS-422 / RS-485*2 Auxiliary function key N/A Calendar Built-in Cooling method Natural cooling CE / UL (please use shielding network cable and magnetic ring with the Approvals filter of 300 ohm / 100 MHz) Panel waterproof level IP65 / NEMA4 DC +24V (-15% to +15%) (please use an isolated power supply) Operation voltage*2 Supplied by Class 2 or SELV circuit (isolated from MAINS by double insulation) Leakage current 500 V for 1 minute (between DC24V terminal and FG terminal) AC Power consumption*2 8.5 W (Max) *3 8.76 W (Max) *3 Backup battery 3V lithium battery CR2032 × 1 About 3 years or more at 25°C Backup battery life (subject to operation temperature and condition) Operation temperature 0°C to 50°C (32°F to 122°F) Storage temperature -20°C to +60°C (-4°F to 140°F) 10% to 90% RH [0°C - 40°C], 10% to 55% RH [41°C - 50°C]; Operating environment pollution degree:
2 Conforms to IEC61131-2: continuous vibration 5 Hz - 8.3 Hz with Vibration resistance amplitude 3.5 mm; 8.3 Hz - 150 Hz with amplitude 1G Conforms to IEC60068-2-27: Shock resistance 11 ms, 15 G Peak, in X, Y, Z directions each for 6 times Dimension 215 x 161 x 50 (W) x (H) x (D) mm Mounting dimension 196.9 x 142.9 (W) x (H) mm Weight Approx. 970 g