Delta · 1 стр.

PCC01 Instruction Sheet English 20060310 (EN)

Оригинальное название: PCC01 Instruction Sheet English 20060310

Читать онлайн

Похожие инструкции

Текст документа

DVP-SA/SX/SC 1 min. 10 sec. 1 min. 15 sec. 1 min. 5 sec. 1 min. 10 sec. DVP-EH/SV 2 min. 50 sec. 3 min. 1 min. 10 sec. 1 min. 20 sec. Make sure PCC01 model record is compatible with PLC model. PCC01 doesn’t contain a valid program for “WR” mode. PCC01 in “WR” mode, and PLC is in RUN mode. Please place PLC in STOP mode. Communication protocol error! Please confirm the PLC is in STOP mode and reboot the PLC. Check PLC program syntax. PLC protect with password. Communication protocol error! Please confirm PLC in STOP mode and remove/apply power to. PCC01 is in “RD” mode, and is protected by password. Please push erase button when PCC01 connect to the PLC.

For more detailed operation of erasure, please reference to section 3.4. PCC01 is in “WR” mode, and PLC is protected by password. Please disable the password in PLC, or set the same PLC’s password in the PCC01. For more detailed operation , please reference to section 3.2. z Disconnecting the PCC01 or powering down the PLC when the operation in progress will cause unexpected The password composed of 4 bytes. Each byte is an ASCII character of ‘0’~’9’, ‘A’~’Z’. ‘a’ ~’z’. The password is case Read Write Read Write DVP-ES/EX/SS 35 sec. 45 sec. 30 sec. 35 sec. error Off PCC01 hardware may be damaged, please replace it.

HEX 3 4 5 6 7 8 9 A B C D E F ASCII ⌧ ⌧ ⌧ ⌧ ⌧ ⌧ ⌧ ⌧ ⌧ ⌧ ⌧ ⌧ ⌧ HEX 13 14 15 16 17 18 19 1A 1B 1C 1D 1E 1F ASCII ⌧ ⌧ ⌧ ⌧ ⌧ ⌧ ⌧ ⌧ ⌧ ⌧ ⌧ ⌧ ⌧ HEX 23 24 25 26 27 28 29 2A 2B 2C 2D 2E 2F ASCII # $ % & ' ( ) * + , - . / HEX 33 34 35 36 37 38 39 3A 3B 3C 3D 3E 3F ASCII 3 4 5 6 7 8 9 : ; = > ? HEX 43 44 45 46 47 48 49 4A 4B 4C 4D 4E 4F ASCII C D E F G H I J K L M N O HEX 53 54 55 56 57 58 59 5A 5B 5C 5D 5E 5F ASCII P S T U V W X Y Z ⌧ ⌧ ⌧ ⌧ ⌧ HEX 63 64 65 66 67 68 69 6A 6B 6C 6D 6E 6F ASCII C d e f g h i j k l M n o HEX 73 74 75 76 77 78 79 7A 7B 7C 7D 7E 7F ASCII s t u v w x y z { | } ~ ⌧ M1085=OFF M1085=ON PCC01 data will be invalid. Please reboot the PLC again or re-connect PCC01 to PLC.

PLC program will be invalid. Please reboot PLC again or re-connect the PCC01 to PLC. 6 Appendix: ASCII Table OK Recommend ERASE completed Off On Please refer to section 3.5. 4 Error Indication PCC01 will show an error or warning status with the ERR and OK LEDs. 5 Troubleshooting z If ERR LED is always ON or blinking. Please refer to section 4. Note: ‘ ⌧ ’ : Denotes invalid ASCII character, do not use. Incompatible model Off to write Synchronous blinking to read Cross blinking Blinking Indicator „ „ z Model results:

simultaneously in WR mode and PLC is in RUN status, user can press the ERASE button within 30 seconds to force completed, push ERASE within 30 seconds while PCC01’s OK LED is ON to switch PLC status from STOP to RUN. Once PCC01 connects to PLC, please press and hold the ERASE button within 5 secs. Continue to hold the button write the data depending on the operation selected. If M1085 is ON he PCC01 will not read or write the data.

High byte Low byte Byte 3 Byte 4 3 (0x33=H33) 4 (0x34=H34) PLC Status w/o PW w/ PW w/o PW w/ PW w/o PW Able to read Password verify error Unable to write RUN w/ PW Unable to read Unable to read Unable to write w/o PW Able to read Password verify error Able to write STOP w/ PW Unable to read Unable to read Password verify error PCC01 provide Run/Stop function in DVP-ES/EX/EC series MPUs. When PCC01 ERR and OK LEDs are blinking PLC in STOP After that, disconnect PCC01 from the PLC and then connect to PLC again. Once data write-in is z Besides program transfer, the PCC01 can also read/write register and coil data to/from the PLC.

The PCC01 will monitor coil M1085 to see if it should read/write the data. When M1085 is OFF, the PCC01 will read or D1087 Read Write PCC01 until the OK LED turns on. Release the button and the ACPGMXFER module can now be removed. 2.) Select PCC01 RD/WR switch in reading or writing mode. 3.) Connect PCC01 to PLC COM1 communication port 4.) After operation is completed, “OK” LED will turn on. 3.4 PCC01 force PLC in RUN/STOP status 3.7 Estimation of Read/Write Operating Timing 5.) Disconnect PCC01 from the PLC. 3.5 PCC01 Data Erase function: 3.6 Data Duplication Function 1.) Set M1085 On/Off in PLC z Data Duplication steps:

http://www.delta.com.tw/industrialautomation/ 5011641001-PCE1 DVP-PCC01 Program Transfer Module Instruction Sheet z PCC01 can read or write PLC programs, devices (coils and registers) and passwords to all series of PLC via Models Program (Steps) D register M device File register 1 Set RD/WR switch to “RD” mode Set RD/WR switch to “WR” mode and confirm PLC is STOP status 2 Connect PCC01 to PLC COM1.Reading will start after 5sec. waiting. Set RD/WR switch to “WR” mode and place the PLC RUN/STOP switch in the STOP position. 3 After reading data from PLC, “OK” LED will light Connect PCC01 to PLC COM1.Writing will start after 5 sec. 4 Disconnect PCC01 when read process is done.

Disconnect PCC01 when write process is done. 2006-03-10 Do not disconnect PCC01 before Transmission ends; otherwise, it may cause data loss in the PCC01 DVP-ES/EX/EC/SS 4K D0~D599 M0~M1279 N/A DVP-SA/SX/SC 8K D0~D4999 M0~M4095 1600 DVP-EH/SV 16K D0~D9999 M0~M4095 10000 2. Communication Indicator LED 5. Operation mode: read/write functional switch Step (PLC → PCC01) RD (Read) (PLC ← PCC01) WR (Write) 33 Operation 0 ℃ ~55 ℃ (Temperature), 50~95% (Humidity), Pollution degree 2 Program area PLC device area Device type 3. Operation completed LED 6. PCC01 Data Erase button Resistance International Standard:

IEC1131-2, IEC 68-2-6 ( TEST Fc ) IEC1131-2 & IEC 68-2-27 (TEST Ea) 5 6 DVP-PCC01 3 Operation and Function Description WR RD ERASE 1 2 3 4 66.3 300 1. Power LED 4. Error LED Storage -25 ℃ ~70 ℃ (Temperature), 5~95% (Humidity) 1 Warning Do not change the RD/WR switch during PCC01 operation. 2 Introduction COM. It provides rapidly and safely data transmission to PLC. COM ERR OK Transmission speed 9600 /19200 bps (PB: 9600 bps only) POWER Unit: mm Please set the RD/WR switch before operating the . z Applicable Models and Read/Write Device Types: ESD: ± 4KV Air Discharge EFT: Power Line: 2KV RS: 0.15MHz~80MHz, 10V/m Surge :

± 1KV Write Cycles At Least 10,000 times Data Retention 10 years 3.1 Read/Write Operation Sequence: z Product Profile z Specification Noise Immunity Vibration / Shock Model M1085=OFF M1085=ON Read Write Read Write DVP-ES/EX/SS 35 sec. 45 sec. 30 sec. 35 sec. DVP-SA/SX/SC 1 min. 10 sec. 1 min. 15 sec. 1 min. 5 sec. 1 min. 10 sec. DVP-EH/SV 2 min. 50 sec. 3 min. 1 min. 10 sec. 1 min. 20 sec. Error Message Indicator ERR OK Recommend OK PCC01 Internal memory error On Off PCC01 hardware may be damaged, please replace it. Incompatible model Blinking Off Make sure PCC01 model record is compatible with PLC model.

Operation error – unable to write Synchronous blinking PCC01 doesn’t contain a valid program for “WR” mode. PCC01 in “WR” mode, and PLC is in RUN mode. Please place PLC in STOP mode. Communication protocol error! Please confirm the PLC is in STOP mode and reboot the PLC. Check PLC program syntax. Operation error – unable to read Cross blinking PLC protect with password. Communication protocol error! Please confirm PLC in STOP mode and remove/apply power to. Password verify error On Blinking PCC01 is in “RD” mode, and is protected by password. Please push erase button when PCC01 connect to the PLC. For more detailed operation of erasure, please reference to section 3.4.