User Manual of A90 Series Inverter 127 ( 0x7F ) Common function code 110 ( 0x6E ) 100 ( 0x64 ) User-defined function code Common function 65 ( 0x41 ) 72 ( 0x48 ) User-defined function code code Common function code 1 ( 0x1 ) Fig. 0-2 Classification of MODBUS Function Codes For example, 12.3.3.1 0x03: function code used to read multiple registers or status words, As shown in Table 0-1, A90 series products mainly involve common function codes . 12.3.3.5 0x06: function code used to write a single register or command, 12.3.3.6 0x10: function code used to write multiple registers or commands, and 12.3.3.4 0x08: function code for diagnosis.
EEPROM storage, the user-defined function codes include 12.3.3.2 0x41: function code In addition, for some specific functions, such as register writing (RAM) without used to write a single register or command (without saving), and 12.3.3.3 0x42: function code used to write multiple registers or commands (without saving). message will be returned (see 0 Exception response). The abnormality function code is When the abnormal valid data is received from a device, a related abnormality defined to distinguish the abnormal data from normal communication data. Corresponding to the normal request function code, the abnormality function code = request function code + 0x80 .
Table 0-1 Function Code Definitions of A90 series Product 273 Function Abnormality Function code function code 03 83 This function code is used to read multiple registers or status words. 41 C1 This function code is used to write a single register or