User Manual of A90 Series Inverter PDU parts are detailed in the following sections, depending on various functions. 12.3.3.1 0x03: function code used to read multiple registers or status words In the remote terminal unit, this function code is used to read the content in the continuous block of the holding register. The request PDU describes the starting register address and the number of registers. The first byte of each register includes high-order bits and the second byte includes The register data in the response message is divided into two bytes in each register. low-order bits.
Request PDU Response PDU N* = number of registers Error PDU Below is an example of a request to read the registers F19.00 to F19.05 (relevant 274 command without saving. 42 C2 This function code is used to write multiple registers or commands without saving. 08 88 This function code is used for diagnosis. 06 86 This function code is used to write a single register or command. 10 90 This function code is used to write multiple registers or commands.
Function code 1 byte 0x03 Starting Address 2 bytes 0x0000 - 0xFFFF Number of registers 2 bytes 1 - 16 Function code 1 byte 0x03 Number of bytes 1 byte 2×N* Register value N*×2 bytes Error code 1 byte 0x83 Exception code 1 byte 01, 02, 03 or 04