User Manual of A90 Series Inverter multiple function codes across groups. However, it is recommended not to read them across groups in the case of no special requirements, so the customer’s software does not need to be upgraded after our products are upgraded. 12.3.3.2 0x41: function code used to write a single register or command (without saving) In the remote terminal unit, this function code is used to write a single non-holding register. The request PDU describes the address to be written to the register. register content is written. The normal response is the response made to the request, which is returned after the  Request PDU  Response PDU  Error PDU “-50.00%”:

Below is an example of a request to change the main frequency source A (7001H) to ★ This function code cannot be used to change the parameters of the attribute “○” 276 Function code 1 byte 0x41 Address of register 2 bytes 0x0000 - 0xFFFF Register value 2 bytes 0x0000 - 0xFFFF Function code 1 byte 0x41 Address of register 2 bytes 0x0000 - 0xFFFF Register value 2 bytes 0x0000 - 0xFFFF Error code 1 byte 0xC1 Exception code 1 byte See Table 0-4 Request Respond Domain name (0x) Domain name (0x) Domain name (0x) (normal) (abnormal) Function 41 Function 41 Function C1 Register address Hi 70 Register address Hi 70 Exception 03 Register address Lo 01 Register address Lo 01 code Register value Hi EC Register value Hi EC Register value Lo 78 Register value Lo 78