User Manual of A90 Series Inverter (it cannot be changed during operation). That is, only the parameters of the attribute “●” (it can be changed during operation) can be changed. Otherwise, the error code 1 will be returned. 12.3.3.3 0x42: function code used to write multiple registers or commands (without saving) In the remote terminal unit, this function code is used to write consecutive non-holding register blocks (1 to 16 registers). The value requested to be written is described in the request data field. The data of each register is divided into two bytes. In the normal response, the function code, starting address and number of registers written will be returned.
Request PDU N* = number of registers Response PDU Error PDU Below is an example of a request to set the acceleration time 1 (F00.14) to 5.00 and deceleration time 1 (F00.15) to 6.00: 277 Function code 1 byte 0x42 Starting Address 2 bytes 0x0000 - 0xFFFF Number of registers 2 bytes 1 - 16 Number of bytes 1 byte 2×N* Register value N*×2 bytes Function code 1 byte 0x42 Starting Address 2 bytes 0x0000 - 0xFFFF Number of 2 bytes 1 - 16 registers Error code 1 byte 0xC2 Exception code 1 byte See Table 0-4 Request Respond Domain name (0x) Domain name (0x) Domain name (0x) (normal) (abnormal) Function 42 Function 42 Function C2