Appendix 6. Data Type Unit: Enum A2_ A-73 Error Code Description Corrective action 16#3619 The station address does not exist. Cause: The station address does not exist. Action: check the address is existed and clear the error and re-execute the function block. 16#3620 The schedule buffer section of SDO is full. Cause: The schedule buffer section of SDO is full. Action: wait till the schedule buffer secton of SDO is less full and re-execute the function block. 16#3622 SDO OD data type is not matched. Cause: SDO OD data type is not matched. Action: check the OD data type is correct and re-execute the function block. 16#3623 SDO is overtime. Cause: SDO is overtime. Action:

check the connection and re-execute the function block. 16#3624 SDO data written error Cause: error occurs in the slave Action: solve the problem and re-execute the function block 16#3625 SDO data reading error Cause: error occurs in the slave Action: solve the problem and re-execute the function block 16#3626 SDO retry time exceeds the setting range. Cause: SDO retry time exceeds the setting range. Action: check the address and re-execute the function block 16#3950 Capture cannot be used when the pulse speed is beyond 1MHz. Cause: Capture cannot be used when the pulse speed is beyond 1MHz Action:

slow dow the pulse speed and re-execute the function block 16#3951 CamCurve wrong input (for example, Concatenate cannot be true or other parameters are out of range.) Cause: CamCurve contact input parameters are out of range Action: (1) turn the PLC off and then on, and execute the DFB CamCure2 and set concatenate option to false. After _ the execution of the function block is done, set the concatenate to true and then execute the DFB CamCure2. _ (2) check the other parameters to see if they are reasonable 16#3953 Capture uses the same channel number repeatedly. Cause: DFB-Capture FB uses the same channel number repeatedly at the same time. Action: use other unused channel number instead.

16#600D The RJ45 port is not connected. (SM1100) Cause: RJ45 prot is not connected. Action: check the communication cable 16#620D The length of the data which needs to be sent in a UDP Socket Configuration window is illegal. 1. Check the program and the related special data registers. 2. Set the Ethernet parameter for the CPU module in HWCONFIG again. 16#6212 There is no response from the remote device after the timeout period. Make sure that the remote device is connected.