AH Motion Controller – Motion control Instructions Manual _A2 A-74 Error Code Description Corrective action 16#6213 The data received exceeds the limit. 1. Check the program and the related special data registers. 2. Set the Ethernet parameter for the CPU module in HWCONFIG again. 16#6214 The remote device refuses the connection. Make sure that the remote device operates normally. 16#6400 The number of TCP connections reaches the upper limit, or the flag which is related to the sending of the data is not set to ON. 1. Check whether the flag which is related to the sending of the data in the program is modified. 2. Retry the setting of the flag and the sending of the packet.
16#6401 The remote device aborts the connection. Check whether the remote device support the MODBUS port (502). 16#6402 There is no response from the remote device after the timeout period. Check whether the remote device operate normally. 16#6403 The remote IP address used in the applied instruction is illegal. Check whether the program is correct. 16#6404 The MODBUS function code not supported is received. Check the command transmitted from the remote device. 16#6405 The number of data which will be received is not consistent with the actual length of the data. Check the command transmitted from the remote device.
16#6501 The remote device involved in the data exchange does not respond after the timeout period. (SM828~SM955) Check the device whose connection number corresponds to the error flag, and check whether it is connected normally. 16#6502 The remote device involved in the data exchange does not respond correctly. (SM828~SM955) Check the device whose connection number corresponds to the error flag, and check whether it is connected normally. 16#6700 MODBUS TCP data exchange initialization error Check the setting value and download the data again. 16#6701 MODBUS TCP data exchange timeout Confirm if the device to be connected supports MODBUS communication protocol.
16#6702 MODBUS TCP data receiving error Confirm if the device to be connected supports MODBUS communication protocol.