Chapter 9 Troubleshooting 9.4.8. AH10PFBM-5A 9_ 9-75 Error code Description Remedy 16#A0F6 Something is wrong with the internal memory of AH10DNET-5A. Supply power to AH10DNET-5A again. If the error still occurs, please contact the factory. 16#A0F7 Something is wrong with the data exchange unit of AH10DNET-5A. Supply power to AH10DNET-5A again. If the error still occurs, please contact the factory. 16#A0F8 The product ID of AH10DNET-5A is incorrect. Supply power to AH10DNET-5A again. If the error still occurs, please contact the factory. 16#A0F9 An error occurs when the data is read from AH10DNET-5A, or when the data is written into AH10DNET-5A. Supply power to AH10DNET-5A again.

If the error still occurs, please contact the factory. 16#A0FA The node ID of AH10DNET-5A is the same as that of the slave set on the scan list. Method 1: Set the node ID of AH10DNET-5A again. The new node ID can not be the same as the node ID of the slave set on the scan list. Supply power to AH10DNET-5A again. Method 2: Put no slave on the scan list, and download the blank scan list to AH10DNET-5A through the simulated online mode in the software. Supply power to AH10DNET-5A again. 16#A0FB The data exchange between AH10DNET and AH CPU failed. Supply power to the AH10DNET and AH CPU and try to exchange data again. If the issue continuses, contact the factory.

16#A0FC Errors occur in the slaves, on the module of an AHRTU-DNET backplane, or on the AHRTU-DNET backplane connection. Check whether the node number has changed. Check if the network connection cable is secured and working fine. Check if the network transmission cable does not exceed the maximum communication distance (refer to AH500 module manual section 10.3.3 for more information). Do not exceed the maximum communication distance to ensure a stable network. Check if the module on the backplane is working fine. Check if the AHRTU-DNET backplane connection is working fine. Error Description Remedy code 16#A001 The master is not set. Download appropriate setting.

16#A003 The master station enters the test mode. Just repower it. 16#A005 A timeout occurs when chips inside the master station communicate. Download the appropriate configuration again. If the error still occurs, please contact the factory. 16#A00B A timeout occurs when AH10PFBM-5A exchanges data exchange with a PLC. Repower AH10PFBM-5A . If the error still occurs, please contact the factory. 16#A402 The PLC does not assign the I/O mapping area to the master. Assign the appropriate I/O mapping area to the master via ISPSoft. 16#A404 Master initializing error Contact the factory if the error still exists after repowering AH10PFBM-5A.