Delta Electronics AH — 9.4.10. AH10COPM-5A

AH Motion Controller – Operation Manual 9.4.9. AH10PFBS-5A 9.4.10. AH10COPM-5A _9 9-76 Error code Description Remedy 16#A406 Internal storage unit error Contact the factory if the error still exists after repowering AH10PFBM-5A. 16#A407 Data exchange unit error Contact the factory if the error still exists after repowering AH10PFBM-5A. 16#A408 Master serial number detection error Contact the factory if the error still exists after repowering AH10PFBM-5A. 16#A4E2 The master detects that the slave is offline. 1. Check whether the PROFIBUS-DP bus connection is normal. 2. Check whether both of the ends of the network have terminal resistors.

16#A4E6 The master detects that an error occurs in the module connected to AHRTU-PFBS-5A. Check the modules connected to AHRTU-PFBS-5A. Error code Description Remedy 16#A4F0 The node address of AH10PFBS-5A exceeds the valid range. The node address of AH10PFBS-5A must be in the range of 1 to 125. 16#A4F1 Internal hardware error If the error still exists after repowering AH10PFBS-5A, replace it with a new one. 16#A4F2 Parameter error Check whether the GSD file AH10PFBS-5A is using is correct. 16#A4F3 Configuration error Check whether the GSD file AH10PFBS-5A is using is correct. 16#A4F4 GPIO detection error If the error still exists after repowering AH10PFBS-5A, replace it with a new one.

16#A4F5 AH10PFBS-5A enters the mode of factory test. Repower AH10PFBS-5A after setting its node address between 1~125. 16#A4F6 1. AH10PFBS-5A has not been connected to the PROFIBUS-DP network. 2. PROFIBUS-DP master has not configured AH10PFBS-5A slave or the configured node address of AH10PFBS-5A is inconsistent with that of the actually connected one. 1. Check whether the communication cable between AH10PFBS-5A and PROFIBUS-DP master is in normal status. 2. Ensure that AH10PFBS-5A slave has been configured to PROFIBUS-DP master and the configured node address of AH10PFBS-5A is consistent with that of the actually connected one. 3. Check whether the PROFIBUS-DP master works normally.

Error code Description Corrective action 16#A0B0 AH10COPM-5A does not send a heartbeat message after a set period of time. Check whether the bus cable on the CANopen network created is connected correctly. 16#A0B1 The length of a PDO that a slave station sends is not the same as the length of the PDO set in the node list. Set the length of the PDO in the slave station again, and then download the setting to AH10COPM-5A.