Chapter 9 Troubleshooting 9_ 9-77 Error code Description Corrective action 16#A0B2 The master station selected does not send a node guarding message after a set period of time. Check whether the bus cable on the CANopen network created is connected correctly. 16#A0E0 AH10COPM-5A receives an emergency message from a slave station. Use the function block CANopen EMCY to read relevant _ information. 16#A0E1 The length of a PDO that a slave station sends is not the same as the length of the PDO set in the node list. Set the length of the PDO in the slave station again, and then download the setting to AH10COPM-5A. 16#A0E2 AH10COPM-5A does not receive a PDO from a slave station.
Make sure that the PDOs in the slave station are set correctly. 16#A0E3 An automatic SDO is not downloaded successfully. Make sure that the automatic SDO is et correctly. 16#A0E4 A PDO parameter is not set successfully. Make sure that the setting of the PDO parameter is legal. 16#A0E5 A key parameter is set incorrectly. Make sure that the slave stations connected are the same as the slave stations set. 16#A0E6 The actual network configuration is not the same as the network configuration set. Make sure that the power supplied to the slave stations connected is normal and the network created is connected correctly.
16#A0E7 The control of the errors in a slave station is not sent after a set period of time. 16#A0E8 The master station address is the same as a slave station address. Set the master station address or the slave station address again, and make sure the new station address is not the same as a slave station address. 16#A0F1 No slave station is added to the node list in CANopen builder. Add slave stations to the node list, and download the configuration to AH10COPM-5A. 16#A0F3 An error occurs in AH10COPM-5A. Download parameters again. If the error still occurs, please replace AH10COPM-5A. 16#A0F4 The bus used is off.
Please check whether the bus cable on the CANopen network created is connected correctly, make sure that the serial transmission speeds of all the nodes on the network are the same, and power AH10COPM-5A again. 16#A0F5 The node address of AH10COPM-5A is set incorrectly. The node address of AH10COPM-5A must be in the range of 1 to 127. 16#A0F6 Internal error: An error occurs in the manufacturing process in the factory. Power AH10COPM-5A again. If the error still occurs, please replace AH10COPM-5A. 16#A0F7 Internal error: GPIO error