Delta Electronics AH — 9.5.1. Software limit errors

AH Motion Controller – Operation Manual 9.5 Troubleshooting for Limitation Errors 9.5.1. Software limit errors The controller system checks the software limits before or during the motion by the error code 0x3911. When the operation exceeds the software limits, the error code will be indicated and the axis will enter “ErrorStop”. Servo drive will not report this error since the error handling in this case is controlled by the controller. Note: for details on the softwaere limit setups, refert to ISPSoft manual. Do not set the values too close to the value of the software upper limit. Error handling process ErrorID 0x3911 State: ErrorStop State:

Standstill In motion Soft limit ON MC_Reset FWD/REV to proper position _9 9-78 Error code Description Corrective action 16#A0F8 Hardware error 16#A0F9 Low voltage Make sure that the power supplied to AH10COPM-5A is normal. 16#A0FA An error occurs in the firmware of AH10COPM-5A. Power AH10COPM-5A again. 16#A0FB The transmission registers in AH10COPM-5A are full. Please make sure that the bus cable on the CANopen network created is connected correctly, and power AH10COPM-5A again. 16#A0FC The reception registers in AH10COPM-5A are full. Please make sure that the bus cable on the CANopen network created is connected correctly, and power AH10COPM-5A again.