Mitsubishi — 5.8.1.1 DeviceNet Connector

Chapter 5 Wiring 5.7.3 Wiring AH04TC-5A Shielded cable *1 Thermocouple CH0 + - ADC INA -150mV~150mV CH3 + - Cold-conjunction compensation *1. The cable connected to the input terminal should be the cable or the shielded twisted pair cable which can be connected to a type J, type K, type R, type S, type T, type E, or type N thermocouple, and should be kept separate from other power cables and cables which generate noise. 5.7.4 Wiring AH08TC-5A Shielded cable *1 Thermoc ouple CH0 + - I0+ ADC INA -150mV~150mV CH7 + - Cold-conjunction compensation *1.

The cable connected to the input terminal should be the cable or the shielded twisted pair cable which can be connected to type J, type K, type R, type S, type T, type E, or type N thermocouple, and should be kept separate from other power cables and cables which generate noise. 5.8 Wiring Network Modules 5.8.1 Wiring AH10DNET-5A 5.8.1.1 DeviceNet Connector 5-53 I0 + I0 - F G I3 + I3 - F G I0 F - G I7 + I7 - F G Pin Signal Color Description 5 4 3 2 1 5 V+ Red 24 VDC 4 CAN H White Signal (positive pole) 3 _ SHIELD - It is connected to a shielded cable. 2 CAN L _ Blue Signal (negative pole) 1 V- Black 0 VDC