Mitsubishi — 5.9.3.2 Ethernet

Chapter 5 Wiring Example: If the node address of AHRTU-PFBS-5A is 26 (decimal value), users have to turn the knob corresponding to x16 1 to position 1, and turn the knob corresponding to x16 0 to position A. 26 (decimal value) = 1A (hexadecimal value)=1Ч16 1 + АЧ16 0 Points for attention:  If users set the node address of AHRTU-PFBS-5A when AHRTU-PFBS-5A is not supplied with power, they have to power AHRTU-PFBS-5A after the node address of AHRTU-PFBS-5A is set.

 If users change the node address of AHRTU-PFBS-5A when AHRTU-PFBS-5A is powered, the change will not take effect immediately after the node address of AHRTU-PFBS-5A is changed, and it will take effect after the users cut off the power supplied to AHRTU-PFBS-5A and then power AHRTU-PFBS-5A again.  To prevent the address knobs on AHRTU-PFBS-5A from being scratched, please carefully use a slotted screwdriver to rotate the address knobs on AHRTU-PFBS-5A. 5.9.3 Wiring AHRTU0-ETHN-5A 5.9.3.1 Connecting the Ethernet Connect the network cable CAT 5e to the RJ-45 port X1 or X2 of the AHRTU-ETHN-5A.

After the CAT 5e is connected to the RJ-45 port of the AHRTU-ETHN-5A, the corresponding lights of RJ-45 port X1 or X2 will be ON. When the linear topology is employed, users can use the RJ-45 port X1 or X2 for establishing connections to other devices and no Ethernet switch is needed. Note: when using port X1 or X2 to make a connection, do not create a loop; otherwise the communication between devices will fail. 5.9.3.2 Ethernet Ethernet port 5-61 Pin Definition Description RJ-45 1 TX+ Transmitting data (positive pole) 2 TX- Transmitting data (negative pole) 3 RX+ Receiving data (positive pole) 4 - - 5 - - 6 RX- Receiving data (negative pole) 7 - - 8 - -