Mitsubishi — 5.10.1 Specifications for Motion Control Modules

AH500 Hardware Manual  AH04HC-5A  AH05PM-5A 5-64 Item Specifications Number of channels 4 channels CH0: X0.8+, X0.8-, X0.9+, and X0.9- CH1: X0.10+, X0.10-, X0.11+, and X0.11- CH2: X0.12+, X0.12-, X0.13+, and X0.13- CH3: X0.14+, X0.14-, X0.15+, and X0.15- Input (differential input) Input signal Pulse/Direction (one phase and one input) Counting up/Counting up (one phase and two inputs) One time the frequency of A/B-phase inputs (two phases and two inputs) Four times the frequency of A/B-phase inputs (two phases and two inputs) Pulse format Signal level 5~24 VDC Maximum The maximum frequency is 200 kHz. frequency of counting The number of sampled pulses is in the range of -200000 to 200000.

The number of accumulated pulses is in the range of -999999999 to 999999999. The number of input pulses is in the range of -2147483648 to 2147483648. Specifications Range Linear count Circular count Type CH0: X0.0+ and X0.0- CH1: X0.1+ and X0.1- CH2: X0.2+ and X0.2- CH3: X0.3+ and X0.3- Input (differential input) RESET input Signal level 5~24VDC Maximum 15 mA current CH0: The high-speed pulse output Y0.8 is a transistor whose collector is an open collector. CH1: The high-speed pulse output Y0.9 is a transistor whose collector is an open collector. CH2: The high-speed pulse output Y0.10 is a transistor whose collector is an open collector. CH3:

The high-speed pulse output Y0.11 is a transistor whose collector is an open collector. Output type Comparison output Signal level 24 VDC Maximum 15 mA current Specifications Item AH05PM-5A Number of actual axes 2 axes Storage The capacity of the built-in storage is 64K steps. Unit Motor unit Compound unit Mechanical unit Users can set the initial register involved in the data exchange in a CPU Connection with a CPU module, and the number of registers involved in the data exchange in the module CPU module. Four hundred data registers at most can be involved in the data exchange. There are three types of pulse output modes. These modes adopt the differential output. Motor control 1.

Pulse/Direction 2. Counting up/Counting down 3. A/B-phase output