Mitsubishi — 9.1.2 ERROR LED Indicator’s Blinking

Chapter 9 Troubleshooting 9-7 Error Description Remedy code 16#2021 The checksum of the command received is incorrect. (SM102/SM103) 1. Check whether there is noise, and retry the sending of the command. 2. Check whether the slave operates normally. 16#2022 The format of the command used in MODRW does not conform to the ASCII format. (SM102/SM103) Make sure that the format of the command conforms to the ASCII format. 16#2023 There is a communication timeout when MODRW is executed. (SM120/SM103) Check whether the slave operates normally, and whether the connection is normal. 16#2024 The setting value of the communication timeout is invalid. (SM120/SM103) 1.

Check the program and the related special data registers. 2. Set the communication port parameter for the CPU module in HWCONFIG again. 16#2025 There is a communication timeout when RS is executed. (SM120/SM103) Check whether the slave operates normally, and whether the connection is normal. 16#2026 The RS communication interrupt is abnormal. (SM120/SM103) Please check whether the interrupt service routine used with RS is downloaded. 16#2027 The execution of FWD is abnormal. (SM102/103) Please refer to AH500 Programming Manual, and check the instruction FWD. 16#2028 The execution of REV is abnormal. (SM102/103) Please refer to AH500 Programming Manual, and check the instruction REV.

16#2029 The execution of STOP is abnormal. (SM102/103) Please refer to AH500 Programming Manual, and check the instruction STOP. 16#202A The execution of RSDT is abnormal. (SM102/103) Please refer to AH500 Programming Manual, and check the instruction RSDT. 16#202B The execution of RSTEF is abnormal. (SM102/103) Please refer to AH500 Programming Manual, and check the instruction RSTEF. 16#202C | 16#204B I/O interrupt service routine 0 | I/O interrupt service routine 31 does not exist.| Please download I/O interrupt service routine 0~31. 16#2054 | 16#2127 I/O interrupt service routine 40 | I/O interrupt service routine 251 does not exist.| Please download I/O interrupt service routine 40~251.

16#2128 An action in a sequential function chart is incorrectly assigned qualifiers related to time. (SM0/SM1) Check whether the action in the sequential function chart is assigned qualifiers related to time. 16#2129 The modifier R is assigned to an action in a sequential function chart incorrectly. (SM0/SM1) Check whether the reset modifier assigned to the action in the sequential function chart conflicts with another modifier assigned to the action in the sequential function chart. 16#6000 Ethernet connection error (SM1106) 1. Check the program and the related special data registers. 2. Set the Ethernet parameter for the CPU module in HWCONFIG again. 16#6001 Illegal IP address (SM1107) 1.

Check the program and the related special data registers. 2. Set the Ethernet parameter for the CPU module in HWCONFIG again.