Kaiyi — 13.8.2 Digital Displayer

Chapter 13 PROFIBUS Slave Module AH10PFBS Indication of options in “Properties—DP slave” dialog box: 13.8 LED Indicator and Troubleshooting 13.8.1 RUN LED and NET LED  RUN LED RUN LED displays the status of the CPU module on the left of AH10PFBS-5A.  NET LED NET LED displays whether the communication between AH10PFBS-5A and PROFIBUS-DP master is working normally. 13.8.2 Digital Displayer  Digital displayer displays the status of AH10PFBS-5A. 13-11 Option Selection Indication Los comm. with master Hold I/O data After AH10PFBS-5A and PROFIBUS-DP master are disconnected, retain the input and output data before disconnection.

Clear I/O data After AH10PFBS-5A and PROFIBUS-DP master are disconnected, the output data is cleared to 0 and the input data is unchanged. LED status Indication How to correct Green light ON PLC is in RUN status. -- OFF The CPU module is in STOP status. Turn the RUN/STOP switch of the CPU module to RUN. LED status Indication How to correct Green light ON Normal -- Red light ON AH10PFBS-5A is not connected to the master. 1. Check if AH10PFBS-5A is connected to PROFIBUS-DP bus. 2. Check if the communication cable between AH10PFBS-5A and PROFIBUS-DP master is in normal status. 3. Check if the actual address of AH10PFBS-5A is consistent with that set in the master configuration software. 4.

Check if the GSD file used is correct. Code Indication How to correct 1~7D When AH10PFBS-5A works normally, the digital displayer displays its node address. -- 80 The CPU module connected to AH10PFBS-5A is in STOP status. Turn the RUN/STOP switch of the CPU module to RUN. F0 The node address of AH10PFBS- 5A exceeds the valid range. Set the node address of AH10PFBS-5A between 1~125. F1 Internal hardware error If the error still exists after repowering AH10PFBS-5A, replace it with a new one. F2 Parameter error Check if the GSD file AH10PFBS-5A is using is correct. F3 Configuration error Check if the GSD file AH10PFBS-5A is using is correct.