Kaiyi — 13.8.3 State Register in AH10PFBS-5A

AH500 Module Manual  The display mechanism of the digital displayer: 1. When AH10PFBS-5A is in normal state and the CPU module is in RUN state, the digital displayer of AH10PFBS-5A only displays the node address. 2. When AH10PFBS-5A is in normal state and the CPU module is in STOP state, the digital displayer of AH10PFBS-5A displays the node address and 80 (the STOP state code of the CPU module) alternately. 3. When AH10PFBS-5A is initializing or in error state and the CPU module is in RUN state, the digital displayer of AH10PFBS-5A displays the node address, initialization code and error code alternately. 4.

When AH10PFBS-5A is initializing or in error state and the CPU module is in STOP state, the digital displayer of AH10PFBS-5A displays the node address, initialization code and 80 (the STOP state code of the CPU module) alternately. 13.8.3 State Register in AH10PFBS-5A The state register in AH10PFBS-5A is used for judging whether the current status of AH10PFBS- 5A is normal. AH10PFBS-5A can specify the state register in hardware configuration via ISPSoft. Double click AH10PFBS-5A icon in HWCONFIG and “Parameter Setting” dialog box pops up then.

Click “Conversion Flags (Read only)” in the left-side blue box as below; then click what the mouse refers to in “Parameter Setting” dialog box; and then the “Address” dialog box appears immediately, where input the number of the specified state register e.g. the input 200 indicates that D200 is the state register. AH10PFBS-5A can only specify D device as its state register. 13-12 Code Indication How to correct F4 GPIO detection error If the error still exists after repowering AH10PFBS-5A, replace it with a new AH10PFBS-5A. F5 AH10PFBS-5A enters the mode of factory test. Repower AH10PFBS-5A after setting its node address between 1~125. F6 1.

AH10PFBS-5A has not been connected to the PROFIBUS- DP network. 2. PROFIBUS-DP master has not configured AH10PFB slave or the configured node address of AH10PFBS-5A is inconsistent with that of the actually connected one. 1. Check if the communication cable between AH10PFBS-5A and PROFIBUS-DP master is in normal status. 2. Ensure that AH10PFBS-5A slave has been configured to PROFIBUS- DP master and the configured node address of AH10PFBS-5A is consistent with that of the actually connected one. 3. Check if PROFIBUS-DP master works normally.