AH500 Module Manual 15-16 Transmission Description Remark type After a TxPDO is changed, and the slave station receives a synchronous message, the new TxPDO will be sent to the master station. The new TxPDO will take effect immediately after the master station receives it. If a TxPDO is not changed, the slave station will not send the TxPDO to the master station. 1 RxPDO A master station sends a synchronous message to a slave station every period of synchronization. The master station sends a RxPDO every period of synchronization. The RxPDO will not take effect until the next synchronous message is received.
Synchronous cyclic TxPDO A master station sends a synchronous message to a slave station every period of synchronization. After the slave station receives a synchronous message, it will send a TxPDO to the master station. The TxPDO will take effect immediately after the master station receives it. 2 RxPDO A master station sends a synchronous message to a slave station every period of synchronization. It sends a RxPDO every two periods of synchronization. The RxPDO that the slave station receives will not take effect until the next synchronous message is received. Synchronous cyclic TxPDO A master station sends a synchronous message to a slave station every period of synchronization.
After the slave station receives two synchronous messages, it will send a TxPDO to the master station. The TxPDO will take effect immediately after the master station receives it. 3~240 They can be described by analogy with RxPDO transmission type 1 and transmission type 2. Synchronous They can be described by analogy with cyclic TxPDO transmission type 1 and transmission type 2. 3~240 254 TxPDO They can be described by analogy with transmission type 1 and transmission type 2. 254 255 RxPDO After a RxPDO is changed, the new RxPDO will be sent to a slave station. The new RxPDO will take effect immediately after the slave station receives it.
If a RxPDO is not changed, it will not be sent to the slave station. Asynchronous TxPDO The value in the Event timer box is 0, and the value in the Inhibit timer box is 0. After a TxPDO is changed, the new TxPDO will be sent to a master station. The new TxPDO will take effect immediately after the master station receives it. If a TxPDO is not changed, it will not be sent to the master station. The value in the Event timer box is not 0, and the value in the Inhibit timer box is not 0. The slave station selected sends a TxPDO to a master station according to the interval set in the Event timer box. (After a TxPDO is sent, it can not be send again during the time set in the Inhibit timer box.
After a TxPDO is changed, the new TxPDO will be send to the master station. The new TxPDO will take effect