Chapter 16 Remote I/O Module AHRTU-ETHN-5A 16.7.2 Error Codes and Trouble-shooting 16.7.2.1 RTU Error 16-27 Error code classification Description 1st Phase 2nd Phase Category Item error software. Extension backplane offline The main backplane and extension backplane are disconnected. Communication error EtherNet/IP error EtherNet/IP communication failure. MODBUS TCP error MODBUS TCP communication failure. NTP error NTP communication failure. Category Error code 7-segment display Explanation How to deal with Hardware error 16#0001 F1 CPU hardware error 1. Re-install the module after power OFF and then check if the error indicator is OFF. 2.
Replace the module and install a new module; check if the error indicator is OFF. 3. Contact the local distributor. 16#0002 F1 Memory hardware error 16#0003 F1 Flash hardware error Hardware error 16#0004 F2 Nework cable link error 1. Check if the connection of two ends of the network cable is proper. 2. Reconnect the network cable and check if the Link LED is ON constantly. 3. Replace the network cable. 16#0005 F1 RTU power supply error (LV1) 1. Check if the supply power is connected properly. 2. Re-install the product and repower on. 3. Contact the local distributor. Configuration error 16#1000 F3 IP address setup error Check if the IP address setup is legal.
16#1001 F4 IP address conflicts 1. Check if there are IP addresses which are repeated in the network. 2. Modify the IP address setup. 16#1002 F5 Network server connection error 1. Check the setup for server connection. 2. Check if the system server exists. 3. Check if the wiring for connecting the server is proper.