Chapter 16 Remote I/O Module AHRTU-ETHN-5A 16.7.3 Indicator Status MS/NS Indicator 16-29 Category Error code 7-segment display Explanation How to deal with timeout 2. Check if the module is normal. 3. Raise the setting value of RPI. 16#3001 E4 DLR link offline Check if Ring network products are connected correctly. MODBUS TCP communication error 16#5000 - Out of connections 1. Check if the number of product connections exceeds the limit. 2. Reduce the number of product connections. NTP communication error 16#5001 - NTP Server connection failure 1. Check the setup for server connection. 2. Check if the system server exists. 3. Check if the wiring for connection of the server is proper.
16#5002 - NTP time update failure 1. Check if the network connection is normal. 2. Check if the NTP parameter setup is correct. LED Status Indication How to deal with MS NS No supply power Check if the supply power works normally. LED OFF LED OFF Green light and Green light and AHRTU initializing No correction red light blink red light blink alternately alternately AHRTU initializing is finished. Green light ON - CPU hardware error 1. Check if the error indicator is OFF after re-installing the module after power OFF. 2. Replace the module and install the new module. Check if the error indicator is OFF. 3. Contact the local distributor.
Memory hardware error Red light ON - Flash hardware error I/O connection is not made. No correction. Green light blinks - I/O connection has been made. Green light ON I/O communication timeout 1. Check if the network cable connection is proper. 2. Check if the module is normal. 3. Raise the setting value of RPI - Red light blinks IP setup error Check if the IP address setup is legal. Red light blinks - - Red light ON IP addresses 1. Check if there are duplicated IP