Mitsubishi — 7.1 Functions of Uniaxial Motion

Chapter 7 Uniaxial Motion the unit selected is a motor unit, users do not need to set SR1002+100*N and SR1003+100*N. 3. Distance generated after the motor of the axis specified rotate once (B) [Description]  Three units are available. They are µm/revolution, mdeg/revolution, and 10 -4 inches/revolution. The unit used is determined by bit 0 and bit 1 in SR1000+100*N. The value in (SR SR1005+100*N, SR1004+100*N) is in the range of 1 to 2,147,483,647.  The unit used is determined by bit 0 and bit 1 in SR1000+100*N. If the unit selected is a mechanical unit or a compound unit, users need to set SR1004+100*N and SR1005+100*N.

If the unit selected is a motor unit, users do not need to set SR1004+100*N and SR1005+100*N. 4. Maximum speed (V MAX ) at which the axis specified rotates [Description]  Users can set the maximum speed of motion. The value in (SR1007+100*N, SR1006+100*N) is in the range of 0 to 2,147,483,647. (The unit used is determined by bit 0 and bit 1 in SR1000+100*N.)  The frequency of pulses generated by motion is in the range of 10 PPS to 1000K PPS. If the value in (SR1007+100*N, SR1006+100*N) is greater than 1000K, the frequency of pulses generated will be 1000K PPS. If the value in (SR1007+100*N, SR1006+100*N) is less than 10, the frequency of pulses generated will be 10 PPS. 5.

Start-up speed (V BIAS ) at which the axis specified rotates [Description]  Users can set the start-up speed of motion. The value in (SR1009+100*N, SR1008+100*N) is in the range of 0 to 2,147,483,647. (The unit used is determined by bit 0 and bit 1 in SR1000+100*N.)  The frequency of pulses generated by motion is in the range of 0 PPS to 1000K PPS. If the value in (SR1009+100*N, SR1008+100*N) is greater than 1000K, the frequency of pulses generated will be 1000K PPS. If the value in (SR1009+100*N, SR1008+100*N) is less than 0, the frequency of pulses generated will be 0 PPS.

 If a stepper motor system is used, the start-up speed that users set must be greater than the motor resonance frequency generated. 6. Time (T ACC ) it takes for the axis specified to accelerate [Description]  Users can set the times it takes for the speed of the axis specified to increase from its start-up speed to its maximum speed. The value in SR1020+100*N is in the range of 0 to 32,767. A millisecond is a unit.  If the value in SR1020+100*N is less than 10, it will be counted as 10. If the value in 7-11 (1+N)th axis HW LW SR1005+100*N SR1004+100*N (1+N)th axis HW LW SR1007+100*N SR1006+100*N (1+N)th axis HW LW SR1009+100*N SR1008+100*N (1+N)th axis HW LW - SR1020+100*N