Mitsubishi — 7.6.2 Operation

Chapter 7 Uniaxial Motion 8. Operation command [Description]  If users want to activate a mode of triggering the return to home, they have to set bit 6 in SR1030+100*N to 1. 7.6.2 Operation  When bit 6 in SR1030+100*N is turned from OFF to ON, a mode of triggering the return to home is activated. The mode of triggering the return to home varies with the present command position of the axis specified. There are two situations. Direction in which the axis specified returns home Limit switch Limit switch LSN DOG LSP [4] [3] [2] [1] Home Position (1): Position [1] is at the right side of the home and DOG, and DOG is OFF. Position (2):

Position [2] is at the right side of the home, and DOG is ON. Position (3): Not supported Position (4): Not supported  Setting parameters There are four modes of stopping the rotation of a motor.  Bit [9:10] in SR1000+100*N is 00.  The mode of returning home is a normal mode, and the return to home is triggered by a transition in DOG’s signal from high to low. 7-23 (1+N)th axis HW LW - SR1030+100*N Special data register SR1030+100*N b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 - - - The execution of the Ox motion subroutine set starts. A mode of inserting two-speed motion is activated. A mode of two-speed motion is activated. A mode of inserting single-speed motion is activated.

A mode of single-speed motion is activated. - A mode of triggering the return to home is activated. A manual pulse generator is operated. A mode of variable motion is activated. The axis specified operates in JOG- mode. The axis specified operates in JOG+ mode. - The motion of the axis specified is stopped by software.