Delta Electronics AH500 — 8.4.6 Online Diagnosis

AH500 Operation Manual The parameters in the hardware shown below are downloaded to the CPU module first. The parameter in AH16AN01R-5A (installed in slot 1) is as follows. Then, AH04HC-5A installed in slot 2 is removed from the actual backplane. The BUS FAULT LED indicator on the CPU module will be ON, that is to say, the hardware configuration in the CPU is different from the actual hardware configuration. Next, I/O Scan is clicked. The scan result will be the same as the actual hardware configuration. After AH16AN01R-5A (installed in slot 1) is double-clicked to open the Parameter Setting window, users will find that the parameter in the module is assigned the default value.

The value of the parameter is different from the value of the parameter previously downloaded to the CPU module, that is to say, only the hardware configuration will be scanned after I/O Scan is clicked. Then, Upload is clicked. After the uploading is complete, users will find that the hardware configuration and the parameters in the modules which are uploaded are the same as the hardware configuration and the parameters in the modules which were previously downloaded to the CPU module. In other words, after Upload is clicked, the system parameters in the CPU module will read, and the actual hardware configuration will not be uploaded.

Next, I/O Scan is clicked, and the scan result is downloaded to the CPU module. The BUS FAULT LED indicator on the CPU module will be OFF, that is to say, the hardware configuration in the CPU module is the same as the actual hardware configuration. 8.4.6 Online Diagnosis Users not only can configure modules in HWCONFIG offline, but also can operate and inspect the system through the Online Mode function if ISPSoft is connected to the CPU module. Owing to the fact that HWCONFIG adopts the communication setting in ISPSoft, users have to make sure that ISPSoft is connected to the CPU module normally before the Online Mode function is enabled.

Please refer to section 2.4 in ISPSoft User Manual for more information about communication setting. If users want to enable the Online Mode function, but the name of the CPU module is different from the name attached to the model in the project management area, the system will remind the users to check the name of the CPU module and the name attached to the model in the project management area. Please refer to section 8.2.2.1 for more information. 8-63