Chapter 7 Temperature Measurement Module AS04/08TC 7_ 7-21 Operand Data type Function Setting range Description connected and counted and each type of modules should be included in the count. CH DWORD/DINT Channel number Channel number for PID algorithm, e.g. channel 1 is number 1 for PID algorithm and channel 2 is number 2 for PID algorithm and so forth. UPDATE BOOL Update PID parameters True:Update PID related parameters in the module, such as PID RUN~CYCLE. _ False: After updating is complete, it refreshes to False. PID RUN _ BOOL Enabling the PID algorithm True: use the PID algorithm. False: reset the output value (MV) to 0, and stop using the PID algorithm.
SV DWORD/DINT Target value -32768~32767 Target value PID MODE _ DWORD/DINT PID control mode 0: Automatic control When PID MAN switches from True _ to False, invoke the output value (MV) in the automatic algorithm. 1: Auto tuning the parameters for the temperature control. After tuning is done, the sysem switches to auto control mode (PID MODE is set to _ 0) and fill in the appropriate parameters (Kc Kp, Ti Ki, Td Kd, _ _ _ Tf, ALPHA and BETA) Note: when the mode is set to 1, auto tuning the parameter, you cannot use numerical value to set up. PID MAN _ BOOL PID A/M mode True: Manual Output the MV according to MOUT. This setting has no effect when PID MODE is set to 1. _