Chapter 8 Load Cell Module AS02LC 8_ 8-7 CR# Name Description Att. Default 3:6 mV/V 4:20 mV/V 5:40 mV/V 6:80 mV/V 61 Sampling cycle for CH2 0:2.5 ms 1:10 ms 2:16 ms 3:20 ms 4:50 ms 5:60 ms 6:100 ms 7:200 ms 8:400 ms R/W 4 62 Weight measured times in a stability range for CH2 Range: K1–K500 R/W 5 63 Stability range for CH2 Floating-point format Range: 0–100000 R/W 10 64 65 Maximum weight for CH2 Floating-point format Maximum measuring weight; when the weight measured exceeds the limit, an alarm is triggered. The value should be greater than 1. R/W 100,000 66 67 Filter mode for CH2 0: no filter (default) 1: maximum filter mode 2: average filter mode R/W 0 68 Maximum filter for CH2 Range:
0–8; the bigger the number the stronger the filter R/W 1 69 Average weight measured times for CH2 Range: 1–100 (for FW V1.04: 1–400 is available) R/W 10 70 Upper limit of the zero return for CH2 Floating-point format Determines the current weight as the zero point in the upper/lower range; when the lower range is larger than the upper range, R/W 10 71 72 Lower limit of the zero return for CH2 R/W -10 73