Chapter 9 Serial Communication Module AS00SCM 9.2.3 Knob Functions Restore default settings: for all communication cards and work mode, you can cut the device power off and turn the knobs to the position F, and resupply the power. The AS00SCM-A module restores back to default setting once it is resupplied with power. This act does NOT affect the communication cards. Cut the power off again and turn the knobs to set the new values and then resupply the power. After that the ASSCCM00-A is set with new settings. Modbus communication (AS-F232/AS-F422/AS-F485): can be installed in Card 1 and Card 2 (in COM mode only). 1.
Use the knob to set the node ID1 and ID2; its setting range is 0x01–0x0F. You can use ISPSoft (HWCONFIG) to set up the node ID, if the knob is turned to 0. Follow the descriptions shown on the HWCONFIG for node ID setting range. mode only). Use the Format Knob to set the communication mode. You can use ISPSoft (HWCONFIG) to set up 2. Modbus communication (AS-F232/AS-F422/AS-F485): can be installed in Card 1 and Card 2 (in COM the communication mode, when the Format Knob is turned to 0. If you need to set the communication mode to UD Link, you need to turn the Format Knob to 0. Refer to section 9.3.2 for more details. CANopen (AS-FCOPM):
can only be installed in Card 2 for COM mode or RTU mode. 1. COM Mode (SCM mode): use the knob to set the node ID and its setting range is 0x01–0x0F. You can use ISPSoft (HWCONFIG) to set up the node ID, when the knob is turned to 0. Follow the descriptions shown on the HWCONFIG for node ID setting range. Thee setting varies according to different CANopen communication mode; refer to section 9.4.1 for more details. 9_ 9-5 ID Setup (AS-F232/AS-F422/AS-F485) COM. RTU ID1/ID2 Node ID Setup ID1/ID2 Node ID Setup 0 Use ISPSoft (HWCONFIG) 1-F Manual Setting Modbus (AS-F232/AS-F422/AS-F485) in COM mode COM.
RTU Format 1/ Format 2 Baud Data (bits) Parity Stop (bits) ASCII/ RTU Format 1/ Format 2 Baud Data (bits) Parity Stop (bits) ASCII/ RTU rate rate (bps) (bps) 0 Software setting 8 38400 8 None 2 RTU 1 9600 7 Even 1 ASCII 9 38400 8 None 1 RTU 2 9600 8 Even 1 RTU A 38400 7 Even 1 ASCII 3 9600 7 None 2 ASCII B 57600 8 None 1 ASCII 4 9600 8 None 1 RTU C 76800 8 None 1 RTU 5 19200 7 Even 1 ASCII D 115200 7 None 1 ASCII 6 19200 8 None 1 RTU E 115200 8 Even 1 RTU 7 19200 8 Odd 2 RTU F 115200 7 None 2 ASCII ID Setup (AS-FCOPM in COM mode) COM. RTU ID2 Node ID Setup ID2 Node ID Setup 0 Use ISPSoft (HWCONFIG) 1-F Manual Setting